Problems in the magnetic flowmeter system are usually indicated by incorrect output readings from the system, error messages, or failed tests. Consider all sources in identifying a problem in your system.
Table
| Local Display Error |
|
|
Message | Message (English) | Potential Cause | Corrective Action |
“Profibus Not | Profibus Not | Profibus segment is disconnected | Connect the Profibus segment |
Communicating” | Communicating | Profibus segment power missing | Verify the segment Profibus voltage |
|
| Electronics failure | Replace electronics |
“Sensor Processor Not | Sensor Comm Err | Transmitter input power (AC/DC) is not | Connect the input power. If the LCD displays a message, |
Communicating” |
| connected | the input power is applied |
|
| Electronics failure | Replace electronics |
“Empty Pipe Detected” | Empty Pipe | Empty Pipe | None - message will clear when pipe is full |
|
| Wiring Error | Check that wiring matches appropriate wiring diagrams - |
|
|
| see Appendix E: Universal Sensor Wiring Diagrams |
|
| Electrode Error | Perform sensor tests C and D (see Table |
|
| Conductivity less than 5 microsiemens | Increase Conductivity to greater than or equal to 5 |
|
| per cm | microsiemens per cm |
|
| Intermittent Diagnostic | Adjust tuning of Empty Pipe parameters |
“Coil Drive Open | Coil Open Ckt | Improper wiring | Check coil drive wiring and sensor coils |
Circuit” |
|
| Perform sensor test A - Sensor Coil |
|
| Other manufacturer’s sensor | Change coil current to 75 mA |
|
|
| Perform a Universal Auto Trim to select the proper coil |
|
|
| current |
|
| Circuit Board Failure | Replace Rosemount 8732 Electronics |
|
| Coil Circuit OPEN Fuse | Return to factory for fuse replacement |
“Auto Zero Failure | Auto Zero Fail | Flow is not set to zero | Force flow to zero, perform autozero |
(Cycle power to clear |
| Unshielded cable in use | Change wire to shielded cable |
messages, no changes |
| Moisture problems | See moisture problems in “Accuracy Section” |
were made)” |
| Empty pipe is present | Fill sensor with process fluid |
“Universal Trim Failure” | Univ Trim Fail | No flow in pipe while performing | Establish a known flow in sensor, and perform Universal |
|
| Universal Auto Trim | |
|
| Wiring error | Check that wiring matches appropriate wiring diagrams - |
|
|
| see “Universal Sensor Wiring Diagrams” on page |
|
| Flow rate is changing in pipe while | Establish a constant flow in sensor, and perform Universal |
|
| performing Universal | |
|
| Flow rate through sensor is | Verify flow in sensor and perform Universal |
|
| significantly different than value | calibration |
|
| entered during Universal |
|
|
| routine |
|
|
| Incorrect calibration number entered | Replace sensor calibration number with |
|
| into transmitter for Universal | 1000005010000001 |
|
| routine |
|
|
| Wrong sensor size selected | Correct sensor size setting - See “Line Size” on page |
|
| Sensor failure | Perform sensor tests C and D (see Table |
“Electronics Failure” | Electronics Fail | Electronics self check failure | Replace Electronics |
“Electronics | Temp Out of Rng | Ambient temperature exceeded the | Move transmitter to a location with an ambient |
Temperature Out of |
| electronics temperature limits | temperature range of |
Range” |
|
|
|
“Reverse Flow | Reverse Flow | Electrode or coil wires reverse | Verify wiring between sensor and transmitter |
Detected” |
| Flow is reverse | Turn ON Reverse Flow Enable to read flow |
|
| Sensor installed backwards | |
|
|
| wires (18 and 19) or the coil wires (1 and 2) |
“Sensor Hi Limit | Flow >Sens limit | Flow rate is greater than 43 ft/sec | Lower flow velocity, increase pipe diameter |
Exceeded” |
| Improper wiring | Check coil drive wiring and sensor coils |
|
|
| Perform sensor test A - Sensor Coil (see Table |
|
|
| page |
|
|
|