Rosemount 8732

Reference Manual

00809-0100-4665, Rev AA August 2010

Absolute

Parameter

Description

Index

33

FSAFE_ TYPE

Defines the reaction of device, if a fault is detected.

 

 

The calculated ACTUAL MODE remains in AUTO.

 

 

0: value FSAFE_VALUE is used as OUT

 

 

Status - UNCERTAIN_Substitute Value,

 

 

1: use last stored valid OUT value

 

 

Status - UNCERTAIN_LastUsableValue

 

 

if there is no valid value available, then

 

 

UNCERTAINInital_Value, OUT value is = Initial

 

 

value

 

 

2: OUT has the wrong calculated value and status

 

 

Status - BAD_* (* as calculated)

34

FSAFE_VALUE

Default value for the OUT parameter, if a sensor or

 

 

sensor electronic fault is detected. The unit of this

 

 

parameter is the same as the OUT parameter.

35

ALARM_HYS

Within the scope of the PROFIBUS-PA specification

 

 

for transmitters there are functions for the

 

 

monitoring of limit violation (off-limit conditions) of

 

 

adjustable limits. Maybe the value of one process

 

 

variable is just the same as the value of a limit and

 

 

the variable fluctuates around the limit it will occur a

 

 

lot of limit violations. That triggers a lot of

 

 

messages; so it must be possible to trigger

 

 

messages only after crossing an adjustable

 

 

hysteresis. The sensitivity of triggering of the alarm

 

 

messages is adjustable. The value of the hysteresis

 

 

is fixed in ALARM_HYS and is the same for the

 

 

parameters HI_HI_LIM, HI_LIM, LO_LIM and

 

 

LO_LO_LIM. The hysteresis is expressed as value

 

 

below high limit and above low limit in the

 

 

engineering unit of xx_LIM.

36

RESERVED

 

 

 

 

37

HI_HI_LIM

Value for upper limit of alarms

 

 

 

38

RESERVED

 

 

 

 

39

HI_LIM

Value for upper limit of warnings

 

 

 

40

RESERVED

 

 

 

 

41

LO_LIM

Value for lower limit of warnings

42

RESERVED

 

43

LO_LO_LIM

Value for the lower limit of alarms

44RESERVED

45RESERVED

46RESERVED

47RESERVED

48RESERVED

49RESERVED

50

SIMULATE

For commissioning and test purposes the input

 

 

value from the Transducer Block in the Analog Input

 

 

Function Block AI-FB can be modified. That means

 

 

that the Transducer and AI-FB will be disconnected.

51-60

RESERVED BY PNO

 

61

VIEW_1_AI

 

3-4

Page 24
Image 24
Emerson Rosemount 8732 manual Reserved Hihilim