Rosemount 8732
Reference Manual
Absolute | Parameter | Description |
Index | ||
33 | FSAFE_ TYPE | Defines the reaction of device, if a fault is detected. |
|
| The calculated ACTUAL MODE remains in AUTO. |
|
| 0: value FSAFE_VALUE is used as OUT |
|
| Status - UNCERTAIN_Substitute Value, |
|
| 1: use last stored valid OUT value |
|
| Status - UNCERTAIN_LastUsableValue |
|
| if there is no valid value available, then |
|
| UNCERTAINInital_Value, OUT value is = Initial |
|
| value |
|
| 2: OUT has the wrong calculated value and status |
|
| Status - BAD_* (* as calculated) |
34 | FSAFE_VALUE | Default value for the OUT parameter, if a sensor or |
|
| sensor electronic fault is detected. The unit of this |
|
| parameter is the same as the OUT parameter. |
35 | ALARM_HYS | Within the scope of the |
|
| for transmitters there are functions for the |
|
| monitoring of limit violation |
|
| adjustable limits. Maybe the value of one process |
|
| variable is just the same as the value of a limit and |
|
| the variable fluctuates around the limit it will occur a |
|
| lot of limit violations. That triggers a lot of |
|
| messages; so it must be possible to trigger |
|
| messages only after crossing an adjustable |
|
| hysteresis. The sensitivity of triggering of the alarm |
|
| messages is adjustable. The value of the hysteresis |
|
| is fixed in ALARM_HYS and is the same for the |
|
| parameters HI_HI_LIM, HI_LIM, LO_LIM and |
|
| LO_LO_LIM. The hysteresis is expressed as value |
|
| below high limit and above low limit in the |
|
| engineering unit of xx_LIM. |
36 | RESERVED |
|
|
|
|
37 | HI_HI_LIM | Value for upper limit of alarms |
|
|
|
38 | RESERVED |
|
|
|
|
39 | HI_LIM | Value for upper limit of warnings |
|
|
|
40 | RESERVED |
|
|
|
|
41 | LO_LIM | Value for lower limit of warnings |
42 | RESERVED |
|
43 | LO_LO_LIM | Value for the lower limit of alarms |
44RESERVED
45RESERVED
46RESERVED
47RESERVED
48RESERVED
49RESERVED
50 | SIMULATE | For commissioning and test purposes the input |
|
| value from the Transducer Block in the Analog Input |
|
| Function Block |
|
| that the Transducer and |
RESERVED BY PNO |
| |
61 | VIEW_1_AI |
|