International Certifications
IECEx
E7 IECEx Flameproof Certificate No.: KEM 07.0038X
Ex de IIC T6 Gb or Ex de [ia Ga] IIC T6 Gb
Vmax = 250 V AC or 42 V DC
EF IECEx Flameproof Certificate No.: KEM 07.0038X
Ex de IIB T6 Gb or Ex de [ia IIC Ga] IIB T6 Gb
Vmax = 250 V AC or 42 V DC
NF IECEx Dust Certificate No.: KEM 07.0038X Ex tD A20 IP66 T 100 °C
with I.S.: Ex tD A20 IP66 T 100 °C [Ex ia Ga] IIC
T6
Special conditions for safe use (KEM 07.0038X):
Contact Rosemount Inc. for information on the dimensions of the flameproof joints. The property class of the security screws which attach the flowtube or junction box to the transmitter is SST
Installation Instructions:
The cable and conduit entry devices and blanking elements shall be of a certified flameproof or increased safety type, suitable for the conditions of use and correctly installed. With the use of conduit, a certified stopping box shall be provided immediately to the entrance of the enclosure.
N7 IECEx Type n Certificate No: IECEx BAS 07.0062X
Ex nA nL [ia] IIC T4
Vmax = 42 V DC
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500V insulation test required by Clause 6.8.1 of IEC
NEPSI - China
E3 NEPSI Flameproof Certificate No.: GYJ071438X Ex de IIC or Ex de [ia] IIC T6
Vmax = 250 V AC or 42 V DC
EP NEPSI Flameproof Certificate No.: GYJ071438X Ex de IIB or Ex de [ia] IIB T6
Vmax = 250 V AC or 42 V DC