Reference Manual
Rosemount 8732
KROHNE SENSORS
Krohne Sensor to Rosemount 8732 Transmitter
Connect coil drive and electrode cables as shown in Figure
Figure E-18. Generic Wiring Diagram for Krohne Sensors and Rosemount 8732
Table E-19. Krohne Sensor Wiring Connections
| KROHNE | ROSEMOUNT 8732 |
| TRANSMITTER | |
| SENSORS | |
|
| |
Electrodes | 3 |
|
2 |
| |
|
| |
| Electrode Shield |
|
Coils | Coil Shield |
|
7 |
| |
|
| |
| 8 |
|
| Fuse |
|
Rosemount 8732 |
| Krohne Sensors | ||||
1 |
|
| 8 | |||
2 |
|
| 7 | |||
|
|
|
|
|
| Coil Shield |
|
|
|
|
| ||
17 |
|
| Electrode Shield | |||
18 |
| 2 | ||||
19 |
| 3 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor or to terminals 1 and 2 of the transmitter, or replacement of the electronics board will be necessary.