Rosemount 8732

Series 2800 Sensor to 8732 Transmitter

Connect coil drive and electrode cables as shown in Figure E-14.

Figure E-14. Wiring Diagram for Foxboro Series 2800 and Rosemount 8732

Table E-15. Foxboro Series

2800 Sensor Wiring

Connections

FOXBORO SERIES

ROSEMOUNT 8732

1800 SENSOR

TRANSMITTER

Electrode Connections

 

Outer Shield

 

White Lead

White

White Shield

Black

 

 

Any Shield

Black Lead

 

Black Shield

 

Inner Shield

 

L2

 

L1

 

Chassis Ground

 

Coil Connections

 

Rosemount 8732

Foxboro Series 2800 Sensors

1

L1

2

L2

 

Chassis Ground

17

Any Shield

18

Black

19

White

This is a pulsed DC magnetic flowmeter.

Do not connect AC power to the sensor or to terminals 1 and 2 of the transmitter, or replacement of the electronics board will be necessary.