Rosemount 8732
Reference Manual
MODULE RELATED INFORMATION
DESCRIPTION OF
EXTENDED DP
FEATURES
DESCRIPTION OF PHYSICAL INTERFACE FOR ASYNC. AND SYNC. TRANSMISSION
DESCRIPTION OF
DEVICE RELATED
DIAGNOSIS
Modular Station | 1; 1: Modular Device | ||
MaxModule | 4 | ;No. of(AI + Totalizer): | |
Max Input Len | 20 ; Max Module x 5 Bytes - 5 * (1 AI + 3 TOT) | ||
|
|
| |
Max Output Len | 6 | ; No. of TOT x 2 Bytes - 2 * (3 TOT) | |
Max Data Len | 6 | ; Max_Input_Length + Max Output Length | |
Slave Family | 12 ;Definition for Profibus PA | ||
Profile(independent\;of used Physicsl layer) | |||
| |||
| 20 ;6 bytes (Standard Diagnostics) + 1 | ||
Max Diag Data Len | Byte\;(Ext.Diag. Header) + 7 Bytes (Ext. | ||
Diag.\;Std.) + 2 Bytes (Ext. Diag. | |||
| |||
| Manufacturer) | ||
|
|
| |
Ext User Prm Data Const(0) | 3 |
| |
|
| ||
Ext User Prm Data Const(0) | 0x00, 0x00, 0x00 | ||
|
| ||
DPV1_Slave | 1;Device conforms to | ||
C2 Read Write supp | 1 |
| |
C2 Max Data Len | 128 | ||
C2 Read Write required | 1 |
| |
C2 Max Count Channels | 1 |
| |
Max Initiate PDU Length | 52 ; 48(Data) + 4(Header) | ||
C2 Response Timeout | 4000 | ||
DPV1 Data Types | 0 |
| |
|
| ||
REVIEW | Rosemount Device is PA device | ||
Physical_Interface | 0 | ; | |
Transmission Delay 45.45 | 0 |
| |
Reaction Delay 45.4 | 0 |
| |
Transmission Delay 93.75 | 0 |
| |
Reaction Delay 93.75 | 0 |
| |
End Physical Interface |
|
| |
Physical Interface | 1 | ; | |
Transmission Delay 31.25 | 0 |
| |
Reaction Delay 31.25 | 0 |
| |
End Physical Interface |
|
| |
|
| ||
Unit Diag Bit(16) | Error appears | ||
Unit Diag Bit(17) | Error disappears | ||
Unit Diag Bit(24) | Hardware failure electronics | ||
Unit Diag Bit(25) | Hardware failure mechanics | ||
Unit Diag Bit(26) | Motor temperature too high | ||
Unit Diag Bit(27) | Electronic temperature too high | ||
Unit Diag Bit(28) | Memory error | ||
Unit Diag Bit(29) | Measurement failure | ||
Unit Diag Bit(30) | Device not initialized | ||
Unit Diag Bit(31) | Device initialization failed | ||
Unit Diag Bit(32) | Zero point error | ||
Unit Diag Bit(33) | Power supply failed |