Reference Manual

00809-0100-4665, Rev AA August 2010

Rosemount 8732

European Certifications

E1 ATEX Flameproof

Certificate No.: KEMA 07ATEX0073 X II 2G

Ex de IIC or Ex de [ia] IIC T6 (-50°C Ta +60 °C) with LOI (-20°C Ta +60 °C)

Vmax = 250 V AC or 42 V DC

0575

ED ATEX Flameproof

Certificate No.: KEMA 07ATEX0073 X II 2G

Ex de IIB or Ex de [ia] IIB T6 (-50°C Ta +60 °C) with LOI (-20°C Ta +60 °C)

Vmax = 250 V AC or 42 V DC 0575

ND(1) ATEX Dust Certificate No.: KEMA 06ATEX0006

II 1D

Ex tD A20 IP66 T 100 °C with I.S.: [Ex ia] IIC II (1)G

Amb. Temp. Limits: (-20 °C Ta + 65 °C)

Vmax = 250 V AC or 42 V DC IP 66

0575

(1)Max surface temperature is 40 °C above the ambient temperature conditions. Tmax = 100 °C

Special conditions for safe use (KEMA 07ATEX0073 X):

Contact Rosemount Inc. for information on the dimensions of the flameproof joints. The property class of the security screws which attach the flowtube or junction box to the transmitter is SST A2-70, or SST A4-70.

Installation Instructions:

The cable and conduit entry devices and blanking elements shall be of a certified flameproof or increased safety type, suitable for the conditions of use and correctly installed. With the use of conduit, a certified stopping box shall be provided immediately to the entrance of the enclosure.

N1 ATEX Type n Certificate No: BASEEFA 07ATEX0203X

II 3(1)G

Ex nA nL [ia] IIC T4 (-50 °C Ta 60 °C)

with LOI: (-20 °C Ta 60 °C) Vmax = 42 V DC

0575

Special conditions for safe use (x)

The apparatus is not capable of withstanding the 500V insulation test required by Clause 6.8.1 of EN 60079-15: 2005. This must be taken into account when installing the apparatus.

B-3

Page 89
Image 89
Emerson Rosemount 8732 European Certifications, Special conditions for safe use Kema 07ATEX0073, Installation Instructions