Table 6-5. Sensor Test

Test

Sensor

Required

Measuring at

Expected Value

Potential Cause

Corrective Action

Location

Equipment

Connections

A. Sensor

Installed or

Multimeter

1 and 2 = R

2Ω ≤ R 18Ω

• Open or

• Remove and

Coil

Uninstalled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shorted Coil

 

replace sensor

B. Shields to

Installed or

Multimeter

17 and

 

 

 

 

< 0.2Ω

Moisture in

Clean terminal

 

 

 

 

Case

Uninstalled

 

 

 

 

and case

 

 

 

 

terminal block

 

block

 

 

 

 

 

 

 

 

 

• Leaky electrode

• Remove sensor

 

 

 

 

 

 

 

 

 

 

 

 

ground

 

 

 

• Process behind

 

 

 

 

 

17 and case

 

 

 

 

liner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ground

 

 

 

 

 

 

 

C. Coil Shield

Installed or

Multimeter

1 and

 

 

 

 

∞Ω (< 1nS)

Process behind

Remove sensor

 

 

 

 

 

 

to Coil

Uninstalled

 

2 and

 

 

 

 

 

 

∞Ω (< 1nS)

 

liner

 

and dry

 

 

 

 

 

 

 

 

 

 

Leaky electrode

Clean terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture in

 

block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal block

Confirm with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sensor coil test

D. Electrode

Installed

LCR (Set to

18 and 17 = R1

R1 and R2 should be stable

• Unstable R1 or

• Remove coating

Shield to

 

Resistance

19 and 17 = R2

NO:

R1R2

300Ω

 

R values

 

from sensor wall

Electrode

 

and 120 Hz)

 

 

 

 

 

 

 

 

 

 

N5, E5, CD,

 

2

Use bulletnose

 

 

 

 

 

 

 

 

 

 

 

 

confirm coated

 

 

 

 

 

 

 

 

 

 

 

 

 

ED:

R1R2

1500Ω

 

electrode

 

electrodes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shorted

Repeat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electrode

 

measurement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrode not in

Pull sensor,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contact with

 

complete test in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

process

 

Table 6-6and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Empty Pipe

 

Table 6-7 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low conductivity

 

page 6-10out of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leaky electrode

 

line.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To test the sensor, a multimeter capable of measuring conductance in nanosiemens is preferred. Nanosiemens is the reciprocal of resistance.

1nanosiemens

=

1

----------------------------

 

 

1gigaohm

 

or

 

1nanosiemens

=

1

------------------------------

 

 

1 × 109ohm

6-8

Page 72
Image 72