Extreme Networks 17001 Rack-mounting the EPS-LD Power Supply, Attaching the Mounting Bracket

Models: 17001

1 274
Download 274 pages 9.67 Kb
Page 178
Image 178

Installing Summit External Power Supplies

Rack-mounting the EPS-LD Power Supply

NOTE

When installing an EPS-LD in a rack, make sure air vents are not restricted. Allow for elevated ambient operating temperatures when the EPS-LD is installed adjacent to other equipment. Be sure you mount the equipment in the rack so that the load is evenly distributed.

To rack-mount each EPS-LD unit:

1Place the EPS-LD unit upright on a stable surface, with the side you want to face to the front of the switch toward you.

2Remove the mounting bracket kit from the packaging.

3Attach the mounting brackets as follows:

a Place a mounting bracket over the mounting holes on one side of the unit (see Figure 150). b Insert the provided screws and fully tighten them using a screwdriver.

Figure 150: Attaching the Mounting Bracket

Collin's

ES4K026

XM_054

cRepeat steps a and b for the other side of the EPS-LD unit.

4Slide the EPS-LD into a 19-inch rack and secure it using appropriate rack-mount screws.

NOTE

Extreme Networks recommends that you position the EPS-LD so that the output connectors are on the same side as the external connector on the connecting switch. If you mount the EPS-LD with the connectors facing in the opposite direction from the Summit switch connector, leave at least 1 U between the switch and the EPS-LD through which to slide the power cords. Do not route the power cords around the equipment rack.

178

Summit Family Switches Hardware Installation Guide

 

 

Page 178
Image 178
Extreme Networks 17001 manual Rack-mounting the EPS-LD Power Supply, Attaching the Mounting Bracket