Cable assembly, serial RJ11 to DB9

PC with available serial port

Firmware Flashing Procedure

1.Install the MSLUtil.exe on the PC.

2.Copy the firmware image (*.bin) into the same directory that the MSLUtil.exe was installed.

3.Connect the library diagnostic port to the PC using the supplied cable assembly.

4.Start the MSLUtil.exe.

5.Click Connect, select the PC serial port that the cable assembly is connected to, and then click OK.

6.Click Download > Browse. Navigate to the directory with the firmware image *.bin.

7.Click OK. The library firmware automatically updates.

NOTE: If the flash process does not complete, select a lower baud rate option, available under the Connect window, and try again.

8.The library will reboot. Verify that the firmware level has been updated successfully by selecting the Library Info button from the View System Data area of the GUI to view the Firmware Revision.