Parameter Description | Issue 01/06 |
3.16Setpoint source
P1000[3] | Selection of frequency setpoint |
| Min: | 0 | ||
| CStat: | CT | Datatype: U16 | Unit: - | Def: | 2 |
| SETPOINT | Active: first confirm | QuickComm.: Yes | Max: | 77 |
Level
1
Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from the least significant digit (i.e., 0 to 7) and any additional setpoint from the most significant digit (i.e., x0 through to x7).
Possible Settings:
0No main setpoint
1MOP setpoint
2Analog setpoint
3Fixed frequency
4USS on BOP link
5USS on COM link
6CB on COM link
7Analog setpoint 2
10 | No main setpoint | + MOP setpoint | |
11 | MOP setpoint | + MOP setpoint | |
12 | Analog setpoint | + | MOP setpoint |
13 | Fixed frequency | + MOP setpoint | |
14 | USS on BOP link | + MOP setpoint | |
15 | USS on COM link | + MOP setpoint | |
16 | CB on COM link | + MOP setpoint | |
17 | Analog setpoint 2 | + | MOP setpoint |
20 | No main setpoint | + | Analog setpoint |
21 | MOP setpoint | + | Analog setpoint |
22 | Analog setpoint | + | Analog setpoint |
23 | Fixed frequency | + | Analog setpoint |
24 | USS on BOP link | + Analog setpoint | |
25 | USS on COM link | + Analog setpoint | |
26 | CB on COM link | + Analog setpoint | |
27 | Analog setpoint 2 | + | Analog setpoint |
30 | No main setpoint | + | Fixed frequency |
31 | MOP setpoint | + Fixed frequency | |
32 | Analog setpoint | + | Fixed frequency |
33 | Fixed frequency | + | Fixed frequency |
34 | USS on BOP link | + Fixed frequency | |
35 | USS on COM link | + Fixed frequency | |
36 | CB on COM link | + Fixed frequency | |
37 | Analog setpoint 2 | + | Fixed frequency |
40 | No main setpoint | + USS on BOP link | |
41 | MOP setpoint | + USS on BOP link | |
42 | Analog setpoint | + USS on BOP link | |
43 | Fixed frequency | + USS on BOP link | |
44 | USS on BOP link | + USS on BOP link | |
45 | USS on COM link | + USS on BOP link | |
46 | CB on COM link | + USS on BOP link | |
47 | Analog setpoint 2 | + USS on BOP link | |
50 | No main setpoint | + USS on COM link | |
51 | MOP setpoint | + USS on COM link | |
52 | Analog setpoint | + USS on COM link | |
53 | Fixed frequency | + USS on COM link | |
54 | USS on BOP link | + USS on COM link | |
55 | USS on COM link | + USS on COM link | |
57 | Analog setpoint 2 | + USS on COM link | |
60 | No main setpoint | + CB on COM link | |
61 | MOP setpoint | + CB on COM link | |
62 | Analog setpoint | + CB on COM link | |
63 | Fixed frequency | + CB on COM link | |
64 | USS on BOP link | + CB on COM link | |
66 | CB on COM link | + CB on COM link | |
67 | Analog setpoint 2 | + CB on COM link | |
70 | No main setpoint | + | Analog setpoint 2 |
71 | MOP setpoint | + | Analog setpoint 2 |
72 | Analog setpoint | + | Analog setpoint 2 |
73 | Fixed frequency | + | Analog setpoint 2 |
74 | USS on BOP link | + Analog setpoint 2 | |
75 | USS on COM link | + Analog setpoint 2 | |
76 | CB on COM link | + Analog setpoint 2 | |
77 | Analog setpoint 2 | + | Analog setpoint 2 |
110 | MICROMASTER 440 Parameter List |