Issue 01/06 | Parameter Description |
P0708[3] Function of digital input 8 |
| Min: | 0 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 99 |
Level
2
Selects function of digital input 8 (via analog input)
Possible Settings:
0Digital input disabled
1ON/OFF1
2ON reverse /OFF1
3 | OFF2 - coast to standstill |
4OFF3 - quick
9Fault acknowledge
10JOG right
11JOG left
12Reverse
13MOP up (increase frequency)
14MOP down (decrease frequency)
25DC brake enable
29External trip
33Disable additional freq setpoint
99Enable BICO parameterization
Index:
P0708[0] : 1st. Command data set (CDS)
P0708[1] : 2nd. Command data set (CDS)
P0708[2] : 3rd. Command data set (CDS)
Note:
Signals above 4 V are active, signals below 1,6 V are inactive.
Details:
See P0701 (function of digital input 1).
P0719[3] Selection of cmd. & freq. setp. |
| Min: | 0 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 67 |
Level
3
Central switch to select control command source for inverter.
Switches command and setpoint source between freely programmable BICO parameters and fixed command/setpoint profiles. Command and setpoint sources can be changed independently.
The tens digit chooses the command source and the units digit chooses the setpoint source.
Possible Settings: |
| |
0 | Cmd = BICO parameter | Setpoint = BICO parameter |
1 | Cmd = BICO parameter | Setpoint = MOP setpoint |
2 | Cmd = BICO parameter | Setpoint = Analog setpoint |
3 | Cmd = BICO parameter | Setpoint = Fixed frequency |
4 | Cmd = BICO parameter | Setpoint = USS on BOP link |
5 | Cmd = BICO parameter | Setpoint = USS on COM link |
6 | Cmd = BICO parameter | Setpoint = CB on COM link |
7 | Cmd = BICO parameter | Setpoint = Analog 2 setp |
10 | Cmd = BOP | Setpoint = BICO parameter |
11 | Cmd = BOP | Setpoint = MOP setpoint |
12 | Cmd = BOP | Setpoint = Analog setpoint |
13 | Cmd = BOP | Setpoint = Fixed frequency |
15 | Cmd = BOP | Setpoint = USS on COM link |
16 | Cmd = BOP | Setpoint = CB on COM link |
17 | Cmd = BOP | Setpoint = Analog 2 setp |
40 | Cmd = USS on BOP link | Setpoint = BICO parameter |
41 | Cmd = USS on BOP link | Setpoint = MOP setpoint |
42 | Cmd = USS on BOP link | Setpoint = Analog setpoint |
43 | Cmd = USS on BOP link | Setpoint = Fixed frequency |
44 | Cmd = USS on BOP link | Setpoint = USS on BOP link |
45 | Cmd = USS on BOP link | Setpoint = USS on COM link |
46 | Cmd = USS on BOP link | Setpoint = CB on COM link |
47 | Cmd = USS on BOP link | Setpoint = Analog 2 setp |
50 | Cmd = USS on COM link | Setpoint = BICO parameter |
51 | Cmd = USS on COM link | Setpoint = MOP setpoint |
52 | Cmd = USS on COM link | Setpoint = Analog setpoint |
53 | Cmd = USS on COM link | Setpoint = Fixed frequency |
54 | Cmd = USS on COM link | Setpoint = USS on BOP link |
55 | Cmd = USS on COM link | Setpoint = USS on COM link |
57 | Cmd = USS on COM link | Setpoint = Analog 2 setp |
60 | Cmd = CB on COM link | Setpoint = BICO parameter |
61 | Cmd = CB on COM link | Setpoint = MOP setpoint |
62 | Cmd = CB on COM link | Setpoint = Analog setpoint |
63 | Cmd = CB on COM link | Setpoint = Fixed frequency |
64 | Cmd = CB on COM link | Setpoint = USS on BOP link |
66 | Cmd = CB on COM link | Setpoint = CB on COM link |
67 | Cmd = CB on COM link | Setpoint = Analog 2 setp |
MICROMASTER 440 | Parameter List | 81 |