Issue 01/06 |
|
|
| Parameter Description | |||
|
|
|
|
| |||
P1582[3] Smooth time for flux setpoint |
| Min: | 4 | Level | |||
| CStat: | CUT | Datatype: U16 | Unit: ms | Def: | 15 | 3 |
|
| ||||||
| CONTROL | Active: Immediately | QuickComm.: No | Max: | 500 |
|
Sets time constant of PT1 filter to smooth flux setpoint.
Index:
P1582[0] : 1st. Drive data set (DDS)
P1582[1] : 2nd. Drive data set (DDS)
P1582[2] : 3rd. Drive data set (DDS)
r1583 | CO: Flux setpoint (smoothed) |
| Min: | - | Level |
| Datatype: Float | Unit: % | Def: | - | 4 |
|
| ||||
|
| Max: | - |
|
Displays smoothed flux setpoint in [%] relative to rated motor flux.
P1596[3] Int. time field weak. controller |
| Min: | 20 | Level | |||
| CStat: | CUT | Datatype: U16 | Unit: ms | Def: | 50 | 3 |
|
| ||||||
| CONTROL | Active: Immediately | QuickComm.: No | Max: | 32001 |
|
Sets integral time for field weakening controller.
Index:
P1596[0] : 1st. Drive data set (DDS)
P1596[1] : 2nd. Drive data set (DDS)
P1596[2] : 3rd. Drive data set (DDS)
r1597 | CO: Outp. field weak. controller |
| Min: | - | Level |
| Datatype: Float | Unit: % | Def: | - | 4 |
|
| ||||
|
| Max: | - |
|
Displays output signal of field weakening controller in [%] relative to rated motor flux.
r1598 | CO: Flux setpoint (total) |
| Min: | - |
| Datatype: Float | Unit: % | Def: | - |
|
| Max: | - |
Level
3
Displays total flux setpoint in [%] relative to the rated motor flux.
P1610[3] Continuous torque boost (SLVC) |
| Min: | 0.0 | ||
CStat: | CUT | Datatype: Float | Unit: % | Def: | 50.0 |
CONTROL | Active: Immediately | QuickComm.: No | Max: | 200.0 |
Level
2
Sets the constant torque boost for the low frequency range when sensorless
For sensorless
isd | f |
P1755 | f(t) |
| |
isd(P1610, P1611) | isd(t) |
P1610 = P1611 = 0
r0331
t P0346
Index:
P1610[0] : 1st. Drive data set (DDS)
P1610[1] : 2nd. Drive data set (DDS)
P1610[2] : 3rd. Drive data set (DDS)
Caution:
P1610 should always be set at least 10% higher than the maximum
Note:
-For P1610 = 0 %, a current setpoint is calculated that corresponds to the
-For P1610 = 100 %, a current setpoint is calculated that corresponds to the rated motor torque.
MICROMASTER 440 | Parameter List |
181 |