Issue 01/06 | Parameter Description |
The actual active command data set (CDS) is displayed in parameter r0050.
| selected | active | |
| CDS | CDS | |
| r0055 | r0054 | r0050 |
| Bit15 | Bit15 |
|
1. CDS | 0 | 0 | 0 |
|
|
|
|
2. CDS | 0 | 1 | 1 |
3. CDS | 1 | 0 | 2 |
3. CDS | 1 | 1 | 2 |
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Example:
Typical procedure for CDS
- CDS1: Command source via terminal and setpoint source via analog input (ADC)
- CDS2: Command source via BOP and setpoint source via MOP - CDS
Steps:
1.Perform commissioning with CDS1 parameters (P0700[0] = 2 and P1000[0] = 2)
2.Connect P0810 (P0811 if necessary) with the source of CDS
3.Copy CDS1 to CDS2 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2)
4.Change CDS2 parameter as required (set parameters for CDS2 [P0700=1 and P1000=1])
DIN4
P0810 = 722.3
Terminals
BOP
ADC
MOP
P0700[0] = 2 | 0 |
P0700[1] = 1 | 1 |
P1000[0] = 2 | 0 |
P1000[1] = 1 | 1 |
Sequence control
Setpoint |
|
| Motor |
channel |
|
| control |
|
| ||
|
|
|
|
Note:
P0811 is also relevant for command data set (CDS) set selection.
P0811 | BI: CDS bit 1 |
|
| Min: | 0:0 | |
| CStat: | CUT | Datatype: U32 | Unit: - | Def: | 0:0 |
| COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4095:0 |
Level
2
Selects command source from which to read Bit 1 for selecting a command data set (see P0810).
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Note:
P0810 is also relevant for command data set (CDS) selection.
MICROMASTER 440 | Parameter List |