3.18Motorized potentiometer (MOP)
P1031[3] Setpoint memory of the MOP |
| Min: | 0 | ||
CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 |
SETPOINT | Active: Immediately | QuickComm.: No | Max: | 1 |
Level
2
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.
Possible Settings:
0MOP setpoint will not be stored
1MOP setpoint will be stored (P1040 is updated)
Index:
P1031[0] : 1st. Drive data set (DDS)
P1031[1] : 2nd. Drive data set (DDS)
P1031[2] : 3rd. Drive data set (DDS)
Note:
On next ON command, motor potentiometer setpoint will be the saved value in parameter P1040 (setpoint of the MOP).
P1032 | Inhibit negative MOP setpoints |
| Min: | 0 | ||
| CStat: | CT | Datatype: U16 | Unit: - | Def: | 1 |
| SETPOINT | Active: first confirm | QuickComm.: No | Max: | 1 |
Level
2
This parameter suppresses negative setpoints of the MOP output r1050.
Possible Settings:
0Neg. MOP setpoint is allowed
1Neg. MOP setpoint inhibited
Note:
The reversing functions (e.g.
P1035[3] BI: Enable MOP |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 19:13 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines source for motor potentiometer setpoint increase frequency.
Index:
P1035[0] : 1st. Command data set (CDS)
P1035[1] : 2nd. Command data set (CDS)
P1035[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.D = MOP up via BOP
Level
3
P1036[3] BI: Enable MOP |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 19:14 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines source for motor potentiometer setpoint decrease frequency.
Index:
P1036[0] : 1st. Command data set (CDS)
P1036[1] : 2nd. Command data set (CDS)
P1036[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E = MOP down via BOP
Level
3