Issue 01/06 | Parameter Description |
3.13Parameter / command / drive data set
P0800[3] BI: Download parameter set 0 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 0:0 |
| COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Level
3
Defines source of command to start download of parameter set 0 from attached AOP.
Index:
P0800[0] : 1st. Command data set (CDS)
P0800[1] : 2nd. Command data set (CDS)
P0800[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
Dependency:
1.The parameter set 0 can only be downloaded in conjunction with the AOP
2.Establish communications between the frequency inverter and AOP
3.The frequency inverter must be selected using the AOP if the AOP is connected at the COM link interface (RS485)
4.Select the frequency inverter state "Ready" (r0002 = 1)
5.Signal from P0800:
0 = Do not download.
1 = Start to download parameter set 0 from the AOP.
Inverter
BI: Dwnl .par.set 0
P0800.C
(0:0)
r0002 = 1
"Drive ready"
&
AOP
BOP link or COM link
Parameter set0
Parameter. set1
.
.
Parameter set9
Transmission of "Parameter set 0" from AOP to inverter
P0801[3] BI: Download parameter set 1 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 0:0 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Level
3
Defines sources of command to start download of parameter set 1 from attached AOP.
Index:
P0801[0] : 1st. Command data set (CDS)
P0801[1] : 2nd. Command data set (CDS)
P0801[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
Note:
See parameter P0800
MICROMASTER 440 | Parameter List |
97 |