Parameter Description | Issue 01/06 |
P2014[2] USS telegram off time |
|
| Min: | 0 | |
CStat: | CT | Datatype: U16 | Unit: ms | Def: | 0 |
COMM | Active: Immediately | QuickComm.: No | Max: | 65535 |
Defines the telegram failure time for the serial interfaces with USS protocol.
Level
3
The telegram failure time defines the time within which a valid telegram must have been received. If a valid telegram is not received within the specified time, the drive inverter outputs fault F0070.
Index:
P2014[0] : Serial interface COM link
P2014[1] : Serial interface BOP link
Notice:
By default (time set to 0), no fault is generated (i.e. watchdog disabled).
r2015[8] CO: PZD from BOP link (USS) |
| Min: | - |
Datatype: U16 | Unit: - | Def: | - |
| Max: | - |
Level
3
Displays process data received via USS on BOP link (RS232 USS).
PZD4 | PZD3 | PZD2 | PZD1 |
STW2 |
| HSW | STW1 |
|
| P2012 |
|
BCC |
| PZD | PKW |
| ADR |
| LGE |
| STX |
| Process data | Parameter |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
USS telegram
r2015 |
| |
| [0] | r2032 |
| [1] |
|
| [2] |
|
. | [3] |
|
|
| |
. |
| r2033 |
. | [7] | |
|
| |
STX | Start of text |
|
LGE | Length |
|
ADR | Address |
|
PKW | Parameter ID value | |
PZD | Process data |
|
BCC | Block check character | |
STW | Control word |
|
HSW | Main setpoint |
|
USS on BOP link PZD mapping to parameter r2015
Index:
r2015[0] : Received word 0
r2015[1] : Received word 1
r2015[2] : Received word 2
r2015[3] : Received word 3
r2015[4] : Received word 4
r2015[5] : Received word 5
r2015[6] : Received word 6
r2015[7] : Received word 7
Note:
The control words can be viewed as bit parameters r2032 and r2033.
Restrictions:
-If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st
-If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd
-When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th
198 | MICROMASTER 440 Parameter List |