Issue 01/06 | Parameter Description |
P1027[3] Fixed frequency mode - Bit 5 |
| Min: | 1 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 1 |
SETPOINT | Active: first confirm | QuickComm.: No | Max: | 2 |
direct selection or direct selection + ON for bit 5
Possible Settings:
1Direct selection
2Direct selection + ON command
Index:
P1027[0] : 1st. Command data set (CDS)
P1027[1] : 2nd. Command data set (CDS)
P1027[2] : 3rd. Command data set (CDS)
Details:
See parameter P1001 for description of how to use fixed frequencies.
Level
3
P1028[3] BI: Fixed freq. selection Bit 5 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 722:5 |
| COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines origin of fixed frequency selection.
Index:
P1028[0] : 1st. Command data set (CDS)
P1028[1] : 2nd. Command data set (CDS)
P1028[2] : 3rd. Command data set (CDS)
Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO).
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings.
Level
3
MICROMASTER 440 | Parameter List |