Issue 01/06 |
|
|
|
| Parameter Description | |||||
|
|
|
|
|
|
|
|
| ||
r0056 |
| CO/BO: Status of motor control |
|
| Min: | - |
| Level | ||
|
|
|
| Datatype: U16 | Unit: - |
| Def: | - |
| 3 |
|
|
|
|
|
|
| ||||
|
| CONTROL |
|
|
| Max: | - |
|
| |
|
| Displays status of motor control (MM420: V/f status), which can be used to diagnose inverter status. | ||||||||
| Bitfields: |
|
|
|
|
|
|
|
| |
|
| Bit00 | Init. control finished |
| 0 | NO | 1 | YES | ||
|
| Bit01 | Motor demagnetizing finished |
| 0 | NO | 1 | YES | ||
|
| Bit02 | Pulses enabled |
|
| 0 | NO | 1 | YES | |
|
| Bit03 | Voltage soft start selected |
| 0 | NO | 1 | YES | ||
|
| Bit04 | Motor excitation finished |
| 0 | NO | 1 | YES | ||
|
| Bit05 | Starting boost active |
| 0 | NO | 1 | YES | ||
|
| Bit06 | Acceleration boost active |
| 0 | NO | 1 | YES | ||
|
| Bit07 | Frequency is negative |
| 0 | NO | 1 | YES | ||
|
| Bit08 | Field weakening active |
| 0 | NO | 1 | YES | ||
|
| Bit09 | Volts setpoint limited |
| 0 | NO | 1 | YES | ||
|
| Bit10 | Slip frequency | limited |
| 0 | NO | 1 | YES | |
|
| Bit11 | F_out > F_max | Freq. limited |
| 0 | NO | 1 | YES | |
|
| Bit12 | Phase reversal selected |
| 0 | NO | 1 | YES | ||
|
| Bit13 |
| 0 | NO | 1 | YES | |||
|
| Bit14 |
| 0 | NO | 1 | YES | |||
|
| Bit15 | KIB |
| 0 | NO | 1 | YES | ||
| Details: |
|
|
|
|
|
|
|
| |
|
| See description of |
|
|
|
|
| |||
r0061 |
| CO: Act. encoder frequency |
|
| Min: | - |
| Level | ||
|
|
|
| Datatype: Float | Unit: Hz |
| Def: | - |
| 2 |
|
|
|
|
|
|
| ||||
|
| CONTROL |
|
|
| Max: | - |
|
| |
|
| Displays actual frequency detected by encoder. |
|
|
|
|
|
| ||
r0062 |
| CO: Freq. setpoint |
|
|
| Min: | - |
| Level | |
|
|
|
| Datatype: Float | Unit: Hz |
| Def: | - |
| 3 |
|
| CONTROL |
|
|
| Max: | - |
|
| |
|
| Displays frequency setpoint of vector controller. |
|
|
|
|
|
| ||
r0063 |
| CO: Act. frequency |
|
|
| Min: | - |
| Level | |
|
|
|
| Datatype: Float | Unit: Hz |
| Def: | - |
| 3 |
|
|
|
|
|
|
| ||||
|
| CONTROL |
|
|
| Max: | - |
|
|
Displays actual unfiltered frequency. This value is not smoothed in contrary to r0021.
Act. frequencies:
V/f
SLVC |
|
|
(Observer |
|
|
model) | r0313 | P0400 |
| ||
|
| |
| 60 ⋅ P0408 |
|
| 0 | 0 |
|
| |
Encoder |
| 1,2 |
|
|
160 ms
P1300
<20
20,22
21,23
60
r0313
Act. filtered speed r0022
Act. filtered frequency r0021
Act. frequency r0063
Act. encoder frequency r0061
P1300 = 21,23 and P0400 = 0
MICROMASTER 440 | Parameter List |
37 |