Issue 01/06 | Parameter Description |
r1343 | CO: Imax controller freq. output |
| Min: | - |
| Datatype: Float | Unit: Hz | Def: | - |
|
| Max: | - |
Level
3
Displays effective frequency limitation.
Dependency:
If I_max controller not in operation, parameter normally shows max. frequency P1082.
r1344 | CO: Imax controller volt. output |
| Min: | - |
| Datatype: Float | Unit: V | Def: | - |
|
| Max: | - |
Level
3
Displays amount by which the I_max controller is reducing the inverter output voltage.
P1345[3] Imax voltage ctrl. prop. gain |
| Min: | 0.000 | ||
CStat: | CUT | Datatype: Float | Unit: - | Def: | 0.250 |
CONTROL | Active: Immediately | QuickComm.: No | Max: | 5.499 |
Level
3
Proportional gain of the I_max voltage controller. See parameter P1340 for further information.
Index: |
|
P1345[0] | : 1st. Drive data set (DDS) |
P1345[1] | : 2nd. Drive data set (DDS) |
P1345[2] | : 3rd. Drive data set (DDS) |
P1346[3] Imax voltage ctrl. integral time |
| Min: | 0.000 | Level | |||
| CStat: | CUT | Datatype: Float | Unit: s | Def: | 0.300 | 3 |
| CONTROL | Active: Immediately | QuickComm.: No | Max: | 50.000 |
|
Integral time constant of the I_max voltage controller.
P1341 = 0 :
I_max frequency and voltage controllers disabled.
P1345 = 0 and P1346 > 0 :
I_max voltage controller enhanced integral
P1345 > 0 and P1346 > 0 :
I_max voltage controller normal PI control
See description in parameter P1340 for further information.
Index:
P1346[0] : 1st. Drive data set (DDS)
P1346[1] : 2nd. Drive data set (DDS)
P1346[2] : 3rd. Drive data set (DDS)
MICROMASTER 440 | Parameter List |
165 |