Issue 01/06 | Parameter Description |
3 Parameter Description
Note
Level 4 Parameters are not visible with BOP or AOP.
3.1Common parameters
r0000 | Drive display |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
|
| Max: | - |
Level
1
Displays the user selected output as defined in P0005.
Note:
Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output frequency, output voltage, output current, and chosen r0000 setting (defined in P0005).
r0002 | Drive state |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
| Max: | - |
Level
2
Displays actual drive state.
Possible Settings:
0Commissioning mode (P0010 != 0)
1Drive ready
2Drive fault active
3Drive starting
4Drive running
5Stopping (ramping down)
Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003 | User access level |
|
| Min: | 0 | |
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 1 |
| ALWAYS | Active: first confirm | QuickComm.: No | Max: | 4 |
Level
1
Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple applications.
Possible Settings:
0User defined parameter list - see P0013 for details on use
1Standard: Allows access into most frequently used parameters.
2Extended: Allows extended access e.g. to inverter I/O functions.
3Expert: For expert use only.
4Service: Only for use by authorized service personal - password protected.
P0004 | Parameter filter |
|
| Min: | 0 | |
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 |
| ALWAYS | Active: first confirm | QuickComm.: No | Max: | 22 |
Filters available parameters according to functionality to enable a more focussed approach to commissioning.
Possible Settings:
0 All parameters
2Inverter
3Motor
4Speed sensor
5Technol. application / units
7Commands, binary I/O
8ADC and DAC
10Setpoint channel / RFG
12Drive features
13Motor control
20Communication
21Alarms / warnings / monitoring
22Technology controller (e.g. PID)
Example:
P0004 = 22 specifies that only PID parameters will be visible.
Level
1
MICROMASTER 440 | Parameter List |
25 |