Parameter Description | Issue 01/06 |
P2222[3] BI: Fixed PID setp. select Bit 2 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 0:0 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines command source of fixed PID setpoint selection Bit 2
Index:
P2222[0] : 1st. Command data set (CDS)
P2222[1] : 2nd. Command data set (CDS)
P2222[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
Level
3
P2223[3] BI: Fixed PID setp. select Bit 3 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 722:3 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines command source of fixed PID setpoint selection Bit 3
Index:
P2223[0] : 1st. Command data set (CDS)
P2223[1] : 2nd. Command data set (CDS)
P2223[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
Level
3
r2224 | CO: Act. fixed PID setpoint |
| Min: | - | Level |
| Datatype: Float | Unit: % | Def: | - | 2 |
|
| ||||
|
|
| Max: | - |
|
Displays total output of PID fixed setpoint selection.
Note:
r2224 = 100 % corresponds to 4000 hex
P2225[3] Fixed PID setpoint mode - Bit 4 |
| Min: | 1 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 1 |
TECH | Active: first confirm | QuickComm.: No | Max: | 2 |
Direct selection or direct selection + ON Bit 4 for PID setpoint.
Possible Settings:
1Direct selection
2Direct selection + ON command
Index:
Level
3
P2225[0] : 1st. Command data set (CDS)
P2225[1] : 2nd. Command data set (CDS)
P2225[2] : 3rd. Command data set (CDS)
P2226[3] BI: Fixed PID setp. select Bit 4 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 722:4 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines command source of fixed PID setpoint selection Bit 4
Index:
P2226[0] : 1st. Command data set (CDS)
P2226[1] : 2nd. Command data set (CDS)
P2226[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
Level
3
228 | MICROMASTER 440 Parameter List |