Parameter Description | Issue 01/06 |
r0633[3] | CO: Rotor winding temperature |
| Min: | - |
| Datatype: Float | Unit: °C | Def: | - |
|
|
| Max: | - |
Level
4
Displays rotor winding temperature of motor mass model.
Index: |
|
r0633[0] | : 1st. Drive data set (DDS) |
r0633[1] | : 2nd. Drive data set (DDS) |
r0633[2] | : 3rd. Drive data set (DDS) |
P0640[3] Motor overload factor [%] |
| Min: | 10.0 | Level | |||
| CStat: | CUT | Datatype: Float | Unit: % | Def: | 150.0 | 2 |
|
| ||||||
| MOTOR | Active: Immediately | QuickComm.: Yes | Max: | 400.0 |
|
Defines motor overload current limit in [%] relative to P0305 (rated motor current).
Index:
P0640[0] : 1st. Drive data set (DDS)
P0640[1] : 2nd. Drive data set (DDS)
P0640[2] : 3rd. Drive data set (DDS)
Dependency:
Limited to maximum inverter current or to 400 % of rated motor current (P0305), whichever is the lower.
P0640max = | min(r0209,4 ⋅ P0305) | ⋅ 100 | |
P0305 | |||
|
|
Details:
See function diagram for current limitation.
74 | MICROMASTER 440 Parameter List |