Issue 01/06 | Parameter Description |
3.17Fixed frequencies
P1001[3] Fixed frequency 1 |
|
| Min: | ||
CStat: | CUT | Datatype: Float | Unit: Hz | Def: | 0.00 |
SETPOINT | Active: Immediately | QuickComm.: No | Max: | 650.00 |
Defines fixed frequency setpoint 1.
There are three options available for selection of the fixed frequencies:
1.Direct selection
2.Direct selection + ON command
3.Binary coded selection + ON command
1.Direct selection (P0701 - P0706 = 15):
-In this mode of operation 1 digital input selects 1 fixed frequency.
-If several inputs are active together, the selected frequencies are summed.
-E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
2.Direct selection + ON command (P0701 - P0706 = 16):
-The fixed frequency selection combines the fixed frequencies with an ON command.
-In this mode of operation 1 digital input selects 1 fixed frequency.
-If several inputs are active together, the selected frequencies are summed.
-E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
3.Binary coded selection + ON command (P0701 - P0706 = 17):
-Up to 16 fixed frequencies can be selected using this method.
-The fixed frequencies are selected according to the following table:
Index:
P1001[0] : 1st. Drive data set (DDS)
P1001[1] : 2nd. Drive data set (DDS)
P1001[2] : 3rd. Drive data set (DDS)
Example:
Binary coded selection :
|
| DIN4 | DIN3 | DIN2 | DIN1 |
0 Hz | FF0 | 0 | 0 | 0 | 0 |
P1001 | FF1 | 0 | 0 | 0 | 1 |
P1002 | FF2 | 0 | 0 | 1 | 0 |
P1003 | FF3 | 0 | 0 | 1 | 1 |
P1004 | FF4 | 0 | 1 | 0 | 0 |
P1005 | FF5 | 0 | 1 | 0 | 1 |
P1006 | FF6 | 0 | 1 | 1 | 0 |
P1007 | FF7 | 0 | 1 | 1 | 1 |
P1008 | FF8 | 1 | 0 | 0 | 0 |
P1009 | FF9 | 1 | 0 | 0 | 1 |
P1010 | FF10 | 1 | 0 | 1 | 0 |
P1011 | FF11 | 1 | 0 | 1 | 1 |
P1012 | FF12 | 1 | 1 | 0 | 0 |
P1013 | FF13 | 1 | 1 | 0 | 1 |
P1014 | FF14 | 1 | 1 | 1 | 0 |
P1015 | FF15 | 1 | 1 | 1 | 1 |
Level
2
MICROMASTER 440 | Parameter List |
113 |