Parameter Description | Issue 01/06 |
P1021[3] BI: Fixed freq. selection Bit 1 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 0:0 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines origin of fixed frequency selection.
Index:
P1021[0] : 1st. Command data set (CDS)
P1021[1] : 2nd. Command data set (CDS)
P1021[2] : 3rd. Command data set (CDS)
Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings
Level
3
P1022[3] BI: Fixed freq. selection Bit 2 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 0:0 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines origin of fixed frequency selection.
Index:
P1022[0] : 1st. Command data set (CDS)
P1022[1] : 2nd. Command data set (CDS)
P1022[2] : 3rd. Command data set (CDS)
Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings
Level
3
P1023[3] BI: Fixed freq. selection Bit 3 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 722:3 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines origin of fixed frequency selection.
Index:
P1023[0] : 1st. Command data set (CDS)
P1023[1] : 2nd. Command data set (CDS)
P1023[2] : 3rd. Command data set (CDS)
Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings
Level
3
r1024 | CO: Act. fixed frequency |
| Min: | - |
| Datatype: Float | Unit: Hz | Def: | - |
|
| Max: | - |
Displays sum total of selected fixed frequencies.
Level
3
P1025[3] Fixed frequency mode - Bit 4 |
| Min: | 1 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 1 |
SETPOINT | Active: first confirm | QuickComm.: No | Max: | 2 |
Direct selection or direct selection + ON for bit 4
Possible Settings:
1Direct selection
2Direct selection + ON command
Index:
P1025[0] : 1st. Command data set (CDS)
P1025[1] : 2nd. Command data set (CDS)
P1025[2] : 3rd. Command data set (CDS)
Details:
See parameter P1001 for description of how to use fixed frequencies.
Level
3
P1026[3] BI: Fixed freq. selection Bit 4 |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 722:4 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines origin of fixed frequency selection.
Index:
P1026[0] : 1st. Command data set (CDS)
P1026[1] : 2nd. Command data set (CDS)
P1026[2] : 3rd. Command data set (CDS)
Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO).
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings.
Level
3
118 | MICROMASTER 440 Parameter List |