Issue 01/06 | Parameter Description |
P0304[3] Rated motor voltage |
|
| Min: | 10 | |
CStat: | C | Datatype: U16 | Unit: V | Def: | 230 |
MOTOR | Active: first confirm | QuickComm.: Yes | Max: | 2000 |
Level
1
Nominal motor voltage [V] from rating plate. Following diagram shows a typical rating plate with the locations of the relevant motor data.
Line supply voltage | 1 AC 110 V *) | 1 AC 230 V | 3 AC 230 V | 3 AC 400 V | 3 AC 500 V |
MICROMASTER 410 | X | X | - | - | - |
MICROMASTER 411 | - | - | - | X | - |
|
|
|
|
|
|
MICROMASTER 420 | - | X | X | X | - |
|
|
|
|
|
|
MICROMASTER 430 | - | - | - | X | - |
|
|
|
|
|
|
MICROMASTER 440 | - | X | X | X | X |
|
|
|
|
|
|
*) Line supply voltage
Index:
P0304[0] : 1st. Drive data set (DDS)
P0304[1] : 2nd. Drive data set (DDS)
P0304[2] : 3rd. Drive data set (DDS)
Dependency:
-Changeable only when P0010 = 1 (quick commissioning).
-Default value is depending on inverter type and its rating data.
Caution:
The input of rating plate data must correspond with the wiring of the motor (star / delta). This means, if delta wiring is used for the motor, delta rating plate data has to be entered.
IEC Motor |
|
|
|
|
|
| W2 | U2 | V2 |
W2 | U2 | V2 |
|
|
|
| U1 | V1 | W1 |
U1 | V1 | W1 |
|
|
U1 |
| U1 |
|
|
|
|
|
| |
V1 |
| V1 |
|
|
W1 |
| W1 |
|
|
Delta connection | Star connection |
e.g.: Volts 230 V (Delta connection) / 400 V (Star connection)
MICROMASTER 440 | Parameter List |
51 |