Parameter Description |
|
|
|
| Issue 01/06 | |
P1210 |
| ON always active (permanent) |
| ON in | ||
| Fault F0003 on | All other faults on | All faults on | No faults on | ||
| Blackout | Brownout | Blackout | Brownout | Blackout | Blackout |
0 | − | − | − | − | − | − |
1 | Fault acknowl. | − | Fault acknowl. | − | Fault acknowl. | − |
2 | Fault acknowl. | − | − | − | − | Restart |
+ | ||||||
| restart |
|
|
|
|
|
3 | Fault acknowl. | Fault acknowl. | Fault acknowl. | Fault acknowl. | Fault acknowl. | − |
+ | + | + | + | + | ||
| restart | restart | restart | restart | restart |
|
4 | Fault acknowl. | Fault acknowl. | − | − | − | − |
+ | + | |||||
| restart | restart |
|
|
|
|
5 | Fault acknowl. | − | Fault acknowl. | − | Fault acknowl. |
|
+ | + | + | Restart | |||
| restart |
| restart |
| restart |
|
6 | Fault acknowl. | Fault acknowl. | Fault acknowl. | Fault acknowl. | Fault acknowl. | Restart |
+ | + | + | + | + | ||
| restart | restart | restart | restart | restart |
|
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or can be driven by the load (P1200).
P1211 | Number of restart attempts |
| Min: | 0 | ||
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 3 |
| FUNC | Active: first confirm | QuickComm.: No | Max: | 10 |
Specifies number of times inverter will attempt to restart if automatic restart P1210 is activated.
Level
3
140 | MICROMASTER 440 Parameter List |