Parameter Description | Issue 01/06 |
P2235[3] BI: Enable |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 19:13 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines source of UP command.
Index:
P2235[0] : 1st. Command data set (CDS)
P2235[1] : 2nd. Command data set (CDS)
P2235[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
19.D = Keypad UP button
Dependency:
To change setpoint:
1.Use UP / DOWN key on BOP or
2.Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
Level
3
P2236[3] BI: Enable |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 19:14 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines source of DOWN command.
Index:
P2236[0] : 1st. Command data set (CDS)
P2236[1] : 2nd. Command data set (CDS)
P2236[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E = Keypad DOWN button
Dependency:
To change setpoint:
1.Use UP / DOWN key on BOP or
2.Set P0702/P0703 = 13/14 (function of digital inputs 2 and 3)
Level
3
P2240[3] Setpoint of |
|
| Min: | ||
CStat: | CUT | Datatype: Float | Unit: % | Def: | 10.00 |
TECH | Active: Immediately | QuickComm.: No | Max: | 200.00 |
Level
2
Setpoint of the motor potentiometer.
Allows user to set a digital PID setpoint in [%].
Index:
P2240[0] : 1st. Drive data set (DDS)
P2240[1] : 2nd. Drive data set (DDS)
P2240[2] : 3rd. Drive data set (DDS)
Note:
P2240 = 100 % corresponds to 4000 hex
230 | MICROMASTER 440 Parameter List |