Issue 01/06 | Parameter Description |
P2201[3] Fixed PID setpoint 1 |
|
| Min: | ||
CStat: | CUT | Datatype: Float | Unit: % | Def: | 0.00 |
TECH | Active: Immediately | QuickComm.: No | Max: | 200.00 |
Defines Fixed PID Setpoint 1
Level
2
There are three options available for selection of the PID fixed setpoints:
1.Direct selection
2.Direct selection + ON command
3.Binary coded selection + ON command
1.Direct selection (P0701 - P0706 = 15):
-In this mode of operation, 1 digital input selects one PID fixed setpoint.
-If several inputs are active together, the selected setpoints are summed.
-E.g.:
2.Direct selection + ON command (P0701 - P0706 = 16):
-In this mode of operation the PID fixed setpoints are combined with an ON command.
-Description as for 1), except that this type of selection issues an ON command concurrent with any setpoint selection.
-If several inputs are active together, the selected setpoints are summed.
-E.g.:
3.Binary coded selection + ON command (P0701 - P0706 = 17):
-Using this method to select the fixed PID setpoint
-The setpoints are selected according to the following table:
Index:
P2201[0] : 1st. Drive data set (DDS)
P2201[1] : 2nd. Drive data set (DDS)
P2201[2] : 3rd. Drive data set (DDS)
Example:
Binary coded selection :
|
| DIN4 | DIN3 | DIN2 | DIN1 |
0 % | PID - FF0 | 0 | 0 | 0 | 0 |
P1001 | PID - FF1 | 0 | 0 | 0 | 1 |
P1002 | PID - FF2 | 0 | 0 | 1 | 0 |
P1003 | PID - FF3 | 0 | 0 | 1 | 1 |
P1004 | PID - FF4 | 0 | 1 | 0 | 0 |
P1005 | PID - FF5 | 0 | 1 | 0 | 1 |
P1006 | PID - FF6 | 0 | 1 | 1 | 0 |
P1007 | PID - FF7 | 0 | 1 | 1 | 1 |
P1008 | PID - FF8 | 1 | 0 | 0 | 0 |
P1009 | PID - FF9 | 1 | 0 | 0 | 1 |
P1010 | PID - FF10 | 1 | 0 | 1 | 0 |
P1011 | PID - FF11 | 1 | 0 | 1 | 1 |
P1012 | PID - FF12 | 1 | 1 | 0 | 0 |
P1013 | PID - FF13 | 1 | 1 | 0 | 1 |
P1014 | PID - FF14 | 1 | 1 | 1 | 0 |
P1015 | PID - FF15 | 1 | 1 | 1 | 1 |
MICROMASTER 440 | Parameter List |
223 |