Issue 01/06 | Parameter Description |
P0308[3] Rated motor cosPhi |
|
| Min: | 0.000 | |
CStat: | C | Datatype: Float | Unit: - | Def: | 0.000 |
MOTOR | Active: first confirm | QuickComm.: Yes | Max: | 1.000 |
Nominal motor power factor (cosPhi) from rating plate - see diagram P0304.
Index:
P0308[0] : 1st. Drive data set (DDS)
P0308[1] : 2nd. Drive data set (DDS)
P0308[2] : 3rd. Drive data set (DDS)
Dependency:
-Changeable only when P0010 = 1 (quick commissioning).
-Visible only when P0100 = 0 or 2, (motor power entered in [kW]).
-Default value is depending on inverter type and its rating data.
Level
1
-Setting 0 causes internal calculation of value. Calculated value see r0332.
P0309[3] Rated motor efficiency |
|
| Min: | 0.0 | |
CStat: | C | Datatype: Float | Unit: % | Def: | 0.0 |
MOTOR | Active: first confirm | QuickComm.: Yes | Max: | 99.9 |
Nominal motor efficiency in [%] from rating plate.
Index:
Level
1
P0309[0] : 1st. Drive data set (DDS)
P0309[1] : 2nd. Drive data set (DDS)
P0309[2] : 3rd. Drive data set (DDS)
Dependency:
-Changeable only when P0010 = 1 (quick commissioning).
-Visible only when P0100 = 1, (i.e. motor power entered in [hp]).
-Default value is depending on inverter type and its rating data.
-Setting 0 causes internal calculation of value. Calculated value see r0332.
Note:
P0309 = 100 % corresponds to superconducting.
Details:
See diagram in P0304 (rating plate).
P0310[3] Rated motor frequency |
|
| Min: | 12.00 | Level | ||
| CStat: | C | Datatype: Float | Unit: Hz | Def: | 50.00 | 1 |
|
| ||||||
| MOTOR | Active: first confirm | QuickComm.: Yes | Max: | 650.00 |
|
Nominal motor frequency [Hz] from rating plate.
Index:
P0310[0] : 1st. Drive data set (DDS)
P0310[1] : 2nd. Drive data set (DDS)
P0310[2] : 3rd. Drive data set (DDS)
Dependency:
-Changeable only when P0010 = 1 (quick commissioning).
-Pole pair number recalculated automatically if parameter is changed.
Details:
See diagram in P0304 (rating plate)
P0311[3] Rated motor speed |
|
| Min: | 0 | |
CStat: | C | Datatype: U16 | Unit: 1/min | Def: | 0 |
MOTOR | Active: first confirm | QuickComm.: Yes | Max: | 40000 |
Nominal motor speed [rpm] from rating plate.
Index:
P0311[0] : 1st. Drive data set (DDS)
P0311[1] : 2nd. Drive data set (DDS)
P0311[2] : 3rd. Drive data set (DDS)
Dependency:
-Changeable only when P0010 = 1 (quick commissioning).
-Setting 0 causes internal calculation of value.
-Slip compensation in V/f control requires rated motor speed for correct operation.
-Pole pair number recalculated automatically if parameter is changed.
-Default value is depending on inverter type and its rating data.
-Required for vector control and V/f control with speed controller.
Details:
See diagram in P0304 (rating plate)
Level
1
MICROMASTER 440 | Parameter List |
53 |