Issue 01/06 | Parameter Description |
P0010 | Commissioning parameter |
| Min: | 0 | ||
| CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
| ALWAYS | Active: first confirm | QuickComm.: No | Max: | 30 |
Level
1
Filters parameters so that only those related to a particular functional group are selected.
Possible Settings:
0Ready
1Quick commissioning
2Inverter
29Download
30Factory setting
Dependency:
- Reset to 0 for inverter to run.
- P0003 (user access level) also determines access to parameters.
Note:
P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be entered one after the other. The end of quick commissioning and the start of internal calculation will be done by setting P3900 = 1 - 3. Afterward parameter P0010 and P3900 will be reset to zero automatically.
P0010 = 2
For service purposes only.
P0010 = 29
To transfer a parameter file via PC tool (e.g.: DriveMonitor, STARTER) parameter P0010 will be set to 29 by the PC tool. When download has been finished PC tool resets parameter P0010 to zero.
P0010 = 30
When resetting the parameters of inverter P0010 must be set to 30. Resetting of the parameters will be started by setting parameter P0970 = 1. The inverter will automatically reset all its parameters to their default settings. This can prove beneficial if you experience problems during parameter setup and wish to start again. Duration of factory setting will take about 60 s.
P0011 | Lock for user defined parameter |
| Min: | 0 | ||
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 |
| FUNC | Active: first confirm | QuickComm.: No | Max: | 65535 |
Details:
See parameter P0013 (user defined parameter)
Level
3
P0012 | Key for user defined parameter |
| Min: | 0 | ||
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 |
| FUNC | Active: first confirm | QuickComm.: No | Max: | 65535 |
Level
3
Details:
See parameter P0013 (user defined parameter).
P0013[20] User defined parameter |
|
| Min: | 0 | Level | ||
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 | 3 |
|
| ||||||
| FUNC | Active: first confirm | QuickComm.: No | Max: | 65535 |
|
Defines a limited set of parameters to which the end user will have access.
Instructions for use:
1.Set P0003 = 3 (expert user)
2.Go to P0013 indices 0 to 16 (user list)
3.Enter into P0013 index 0 to 16 the parameters required to be visible in the
-P0013 index 19 = 12 (key for user defined parameter)
-P0013 index 18 = 10 (commissioning parameter filter)
-P0013 index 17 = 3 (user access level)
4.Set P0003 = 0 to activate the user defined parameter.
MICROMASTER 440 | Parameter List |
27 |