Issue 01/06 | Parameter Description |
3.8Command source
P0700[3] Selection of command source |
| Min: | 0 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 2 |
COMMANDS | Active: first confirm | QuickComm.: Yes | Max: | 6 |
Selects digital command source.
Possible Settings:
0Factory default setting
1BOP (keypad)
2Terminal
4USS on BOP link
5USS on COM link
6CB on COM link
Index:
P0700[0] : 1st. Command data set (CDS)
P0700[1] : 2nd. Command data set (CDS)
P0700[2] : 3rd. Command data set (CDS)
Example:
Changing form P0700 = 1 to P0700 = 2 sets all digital inputs to default settings.
Level
1
BOP |
|
Terminals |
|
USS | P0700 = 2 |
BOP link |
|
USS |
|
COM link |
|
CB |
|
COM link |
|
Sequence control
Setpoint |
|
| Motor |
channel |
|
| control |
|
| ||
|
|
|
|
Caution:
Be aware, by changing of parameter P0700 all BI parameters are reset to the default value or modified as listed in the table below.
If the Inverter is being controlled via the AOP, select USS (with the corresponding interface) for the Command Source. If the AOP is connected to the
Note:
Changing this parameter sets (to default) all settings on item selected (see table).
| P0700 = 0 | P0700 = 1 | P0700 = 2 | P0700 = 4 | P0700 = 5 | P0700 = 6 |
P0701 | 1 | 0 | 1 | 0 | 0 | 0 |
|
|
|
|
|
|
|
P0702 | 12 | 0 | 12 | 0 | 0 | 0 |
|
|
|
|
|
|
|
P0703 | 9 | 9 | 9 | 9 | 9 | 9 |
|
|
|
|
|
|
|
P0704 | 15 | 15 | 15 | 15 | 15 | 15 |
|
|
|
|
|
|
|
P0705 | 15 | 15 | 15 | 15 | 15 | 15 |
P0706 | 15 | 15 | 15 | 15 | 15 | 15 |
P0707 | 0 | 0 | 0 | 0 | 0 | 0 |
|
|
|
|
|
|
|
P0708 | 0 | 0 | 0 | 0 | 0 | 0 |
|
|
|
|
|
|
|
P0731 | 52.3 | 52.3 | 52.3 | 52.3 | 52.3 | 52.3 |
|
|
|
|
|
|
|
P0732 | 52.7 | 52.7 | 52.7 | 52.7 | 52.7 | 52.7 |
P0733 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
|
|
|
|
|
|
|
P0800 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
|
|
|
|
|
|
|
P0801 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
MICROMASTER 440 | Parameter List |
75 |