Issue 01/06 | Parameter Description |
r1084 | Resultant max. frequency |
| Min: | - | ||
|
|
| Datatype: Float | Unit: Hz | Def: | - |
| CONTROL |
|
| Max: | - | |
| Displays resultant maximum frequency. |
|
|
| ||
| P1300 < 20 |
|
|
|
| |
| P1800 ≤ | 6 kHz → | r1084 = min(P1082, P1800 | , 650.00) |
|
|
|
|
| 15 |
|
|
|
| P1800 ≥ | 8 kHz → | r1084 = min (P1082,650.00) |
|
| |
| P1300 ≥ 20 |
|
|
|
| |
| r1084= | min(P1082, 5 ⋅ P0310, 200.00) |
|
|
|
Level
3
P1091[3] Skip frequency 1 |
|
| Min: | 0.00 | |
CStat: | CUT | Datatype: Float | Unit: Hz | Def: | 0.00 |
SETPOINT | Active: Immediately | QuickComm.: No | Max: | 650.00 |
Level
3
Defines skip frequency 1 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).
fout
P1101 |
Skip frequency |
bandwidth |
fin |
P1091 |
Skip frequency |
Index:
P1091[0] : 1st. Drive data set (DDS)
P1091[1] : 2nd. Drive data set (DDS)
P1091[2] : 3rd. Drive data set (DDS)
Notice:
-Stationary operation is not possible within the suppressed frequency range; the range is merely passed through (on the ramp).
-For example, if P1091 = 10 Hz and P1101 = 2 Hz, it is not possible to operate continuously between 10 Hz +/- 2 Hz (i.e. between 8 and 12 Hz).
P1092[3] Skip frequency 2 |
|
| Min: | 0.00 | |
CStat: | CUT | Datatype: Float | Unit: Hz | Def: | 0.00 |
SETPOINT | Active: Immediately | QuickComm.: No | Max: | 650.00 |
Level
3
Defines skip frequency 2 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).
Index:
P1092[0] : 1st. Drive data set (DDS)
P1092[1] : 2nd. Drive data set (DDS)
P1092[2] : 3rd. Drive data set (DDS)
Details:
See P1091 (skip frequency 1).
P1093[3] Skip frequency 3 |
|
| Min: | 0.00 | |
CStat: | CUT | Datatype: Float | Unit: Hz | Def: | 0.00 |
SETPOINT | Active: Immediately | QuickComm.: No | Max: | 650.00 |
Level
3
Defines skip frequency 3 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).
Index:
P1093[0] : 1st. Drive data set (DDS)
P1093[1] : 2nd. Drive data set (DDS)
P1093[2] : 3rd. Drive data set (DDS)
Details:
See P1091 (skip frequency 1).
MICROMASTER 440 | Parameter List |
129 |