Parameter Description | Issue 01/06 |
3.3Inverter parameters (HW)
P0100 | Europe / North America |
|
| Min: | 0 | |
| CStat: | C | Datatype: U16 | Unit: - | Def: | 0 |
| QUICK | Active: first confirm | QuickComm.: Yes | Max: | 2 |
Level
1
Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in [kW] or [hp].
The default settings for the nominal rating plate frequency (P0310) and maximum motor frequency (P1082) are also set automatically here, in addition to reference frequency (P2000).
Possible | Settings: |
|
0 | Europe [kW], | frequency default 50 Hz |
1North America [hp], frequency default 60 Hz
2North America [kW], frequency default 60 Hz
Dependency:
Where:
- Stop drive first (i.e. disable all pulses) before you change this parameter.
- P0100 can only be changed when P0010 = 1 (Commissioning mode) via the respective Commissioing interface (e.g. BOP).
- Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (see P0340 - calculation of motor parameters).
Changing P0100 overwrites the settings of the DIP50/60 switch (location shown in the diagram below):
1.Parameter P0100 has an higher priority than the DIP50/60 switch.
2.However, after the inverter is
3.The DIP50/60 switch does not have any effect, if P0100 = 2.
Remove I/O board
DIP50/60
Power |
|
| Quick |
|
| commissioning | |
cycle |
|
| |
|
| P0010 = 1 | |
|
|
| |
P0100 = 2 | yes | yes | P0100 = 2 |
|
| ||
? |
|
| ? |
no |
|
| no |
|
| no | P0100 = 1 |
|
|
| |
|
|
| ? |
DIP50/60 = | no |
| yes |
|
| ||
50 Hz |
|
|
|
? |
|
|
|
yes |
|
|
|
Power in kW |
| Power in kW |
| Power in hp |
Frequency 50 Hz |
| Frequency 60 Hz |
| Frequency 60 Hz |
|
|
|
|
|
P0100 = 0 |
| P0100 = 2 |
| P0100 = 1 |
Notice:
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see diagram above).
P0199 | Equipment system number |
| Min: | 0 | ||
| CStat: | UT | Datatype: U16 | Unit: - | Def: | 0 |
| - | Active: first confirm | QuickComm.: No | Max: | 255 |
Equipment system number This parameter has no operation effect.
Level
2
42 | MICROMASTER 440 Parameter List |