Issue 01/06 | Parameter Description |
3.35Faults, Alarms, Monitoring
P2100[3] Alarm number selection |
| Min: | 0 | ||
CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
ALARMS | Active: first confirm | QuickComm.: No | Max: | 65535 |
Level
3
Selects up to 3 faults or warnings for
Index:
P2100[0] : Fault Number 1
P2100[1] : Fault Number 2
P2100[2] : Fault Number 3
Example:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0] = 5, then select the desired reaction in P2101[0] (in this case, set P2101[0] = 3).
Note:
All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (e.g. overcurrent) cannot be changed from the default reactions.
P2101[3] Stop reaction value |
|
| Min: | 0 | |
CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
ALARMS | Active: first confirm | QuickComm.: No | Max: | 4 |
Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction).
Level
3
This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
Possible Settings:
0No reaction, no display
1OFF1 stop reaction
2OFF2 stop reaction
3OFF3 stop reaction
4No reaction warning only
Index:
P2101[0] : Stop reaction value 1
P2101[1] : Stop reaction value 2
P2101[2] : Stop reaction value 3
Note:
-Settings 0 - 3 only are available for fault codes.
-Settings 0 and 4 only are available for warnings.
-Index 0 (P2101) refers to fault/warning in index 0 (P2100).
P2103[3] BI: 1. Faults acknowledgement |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 722:2 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines first source of fault acknowledgement, e.g. keypad/DIN, etc. (depending on setting).
Index:
P2103[0] : 1st. Command data set (CDS)
P2103[1] : 2nd. Command data set (CDS)
P2103[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Level
3
MICROMASTER 440 | Parameter List |
207 |