Issue 01/06 | Parameter Description |
3.40Inverter parameters
P3900 | End of quick commissioning |
| Min: | 0 | ||
| CStat: | C | Datatype: U16 | Unit: - | Def: | 0 |
| QUICK | Active: first confirm | QuickComm.: Yes | Max: | 3 |
Performs calculations necessary for optimized motor operation.
Level
1
After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically reset to their original value 0.
Possible Settings:
0No quick commissioning
1Start quick commissioning with factory reset
2Start quick commissioning
3Start quick commissioning only for motor data
Dependency:
Changeable only when P0010 = 1 (quick commissioning)
Note:
P3900 = 1 :
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick commissioning", are retained; all other parameter changes, including the I/O settings, are lost. Motor calculations are also performed.
P3900 = 2 :
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the motor calculations performed.
P3900 = 3 :
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values (see parameter P0340, setting P0340 = 1).
P3950 | Access of hidden parameters |
| Min: | 0 | ||
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 |
| ALWAYS | Active: first confirm | QuickComm.: No | Max: | 255 |
Level
4
Accesses special parameters for development (expert only) and factory functionality (calibration parameter).
r3954[13] CM version and GUI ID |
| Min: | - |
Datatype: U16 | Unit: - | Def: | - |
| Max: | - |
Used to classify firmware (only for SIEMENS internal purposes).
Index:
r3954[0] : CM version (major release)
r3954[1] : CM version (minor release)
r3954[2] : CM version (baselevel or patch)
r3954[3] : GUI ID
r3954[4] : GUI ID
r3954[5] : GUI ID
r3954[6] : GUI ID
r3954[7] : GUI ID
r3954[8] : GUI ID
r3954[9] : GUI ID
r3954[10] : GUI ID
r3954[11] : GUI ID major release
r3954[12] : GUI ID minor release
Level
4
MICROMASTER 440 | Parameter List |
257 |