Parameter Description | Issue 01/06 |
3.10Digital outputs
r0730 | Number of digital outputs |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
| Max: | - |
Displays number of digital outputs (relays).
Level
3
P0731[3] BI: Function of digital output 1 |
| Min: | 0:0 | ||
CStat: | CUT | Datatype: U32 | Unit: - | Def: | 52:3 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Defines source of digital output 1.
Level
2
DOUT channel | Invert DOUTs |
| 0 ... 7 |
| P0748 (0) |
|
| BI: Fct. of DOUT 1 |
|
| |
Function | rxxxx.y | P0731.C | 0 |
| |
|
|
| |||
xxxx .y | (52:3) | 1 | |||
| |||||
|
|
|
| ||
| P0731 = xxxx.y |
|
|
CO/BO: State DOUTs | int. 24 V | |
max. 100 mA | ||
r0747 | ||
Kl.9 | ||
r0747.0 | ||
|
COM | Kl.20 |
NO Kl.19
or
NC Kl.18
Relay : max. load capability | Kl.28 |
DC 30 V / 5 A |
AC 250 V / 2 A max. opening / closing time
5 / 10 ms
Index: |
|
|
|
|
P0731[0] : 1st. Command data set (CDS) |
|
| ||
P0731[1] : 2nd. Command data set (CDS) |
|
| ||
P0731[2] : 3rd. Command data set (CDS) |
|
| ||
Common Settings: |
|
|
| |
52.0 | Drive ready |
| 0 | Closed |
52.1 | Drive ready to run | 0 | Closed | |
52.2 | Drive running |
| 0 | Closed |
52.3 | Drive fault active | 0 | Closed | |
52.4 | OFF2 active |
| 1 | Closed |
52.5 | OFF3 active |
| 1 | Closed |
52.6 | Switch on inhibit active | 0 | Closed | |
52.7 | Drive warning active | 0 | Closed | |
52.8 | Deviation setpoint/actual value | 1 | Closed | |
52.9 | PZD control (Process Data Control) | 0 | Closed | |
52.A | Maximum frequency reached | 0 | Closed | |
52.B | Warning: Motor current limit | 1 | Closed | |
52.C | Motor holding brake (MHB) active | 0 | Closed | |
52.D | Motor overload |
| 1 | Closed |
52.E | Motor running direction right | 0 | Closed | |
52.F | Inverter overload | 1 | Closed | |
53.0 | DC brake active |
| 0 | Closed |
53.1 | Act. freq. f_act | > P2167 (f_off) | 0 | Closed |
53.2 | Act. freq. f_act | <= P1080 (f_min) | 0 | Closed |
53.3 | Act. current r0027 > P2170 | 0 | Closed | |
53.4 | Act. freq. f_act | > P2155 (f_1) | 0 | Closed |
53.5 | Act. freq. f_act | <= P2155 (f_1) | 0 | Closed |
53.6 | Act. freq. f_act | >= setpoint | 0 | Closed |
53.7 | Act. Vdc r0026 < P2172 | 0 | Closed | |
53.8 | Act. Vdc r0026 > P2172 | 0 | Closed | |
53.A | PID output r2294 == P2292 (PID_min) | 0 | Closed | |
53.B | PID output r2294 == P2291 (PID_max) | 0 | Closed |
Details: |
|
Display functions | ==> see parameter r0052, r0053 |
Motor holding brake | ==> see parameter P1215 |
DC brake | ==> see parameter P1232, P1233 |
84 | MICROMASTER 440 Parameter List |