Parameter Description | Issue 01/06 |
P2166[3] Delay time ramp up completed |
| Min: | 0 | ||
CStat: | CUT | Datatype: U16 | Unit: ms | Def: | 10 |
ALARMS | Active: Immediately | QuickComm.: No | Max: | 10000 |
Delay time for signal that indicates completion of
Index:
P2166[0] : 1st. Drive data set (DDS)
P2166[1] : 2nd. Drive data set (DDS)
P2166[2] : 3rd. Drive data set (DDS)
Details:
See diagram in P2174.
Level
2
P2167[3] |
| Min: | 0.00 | ||
CStat: | CUT | Datatype: Float | Unit: Hz | Def: | 1.00 |
ALARMS | Active: Immediately | QuickComm.: No | Max: | 10.00 |
Defines the threshold of the monitoring function f_act <= P2167 (f_off).
Level
3
P2167 influences following functions:
-If the actual frequency falls below this threshold and the time delay has expired, bit 1 in status word 2 (r0053) is reset.
-If a OFF1 or OFF3 was applied and bit 1 is reset the inverter will disable the pulse (OFF2). Restriction:
-The monitoring function f_act <= P2167 (f_off) is not updated and pulses are not disabled, if motor holding brake (MHB, P1215 = 1) is enabled.
ON |
|
|
OFF1/OFF3 |
| t |
f | f act | OFF1/OFF3 |
|
| |
P2167 |
|
|
|
| t |
f_act > P2167 |
|
r0053 1 Bit 01 0
OFF2
Inactive
Active
Index:
t
P2168 | P2168 | P2168 |
t
P2167[0] : 1st. Drive data set (DDS)
P2167[1] : 2nd. Drive data set (DDS)
P2167[2] : 3rd. Drive data set (DDS)
P2168[3] Delay time T_off |
|
| Min: | 0 | |
CStat: | CUT | Datatype: U16 | Unit: ms | Def: | 10 |
ALARMS | Active: Immediately | QuickComm.: No | Max: | 10000 |
Level
3
Defines time for which the inverter may operate below
Index:
P2168[0] : 1st. Drive data set (DDS)
P2168[1] : 2nd. Drive data set (DDS)
P2168[2] : 3rd. Drive data set (DDS)
Dependency:
Active if holding brake (P1215) not parameterized.
Details:
See diagram in P2167
214 | MICROMASTER 440 Parameter List |