Parameter Description | Issue 01/06 |
P2484[3] No. of shaft turns = 1 Unit |
| Min: | 0.01 | ||
CStat: | CUT | Datatype: Float | Unit: - | Def: | 1.00 |
CONTROL | Active: first confirm | QuickComm.: No | Max: | 9999.99 |
Sets the number of rotations of the motor shaft required to represent 1 unit of user selected units.
Pulley radius r |
|
|
| Distance s | ||
|
|
|
|
|
| |
|
|
| Load |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
U
| r |
| o |
| t |
o | |
M |
|
P2484 = | U | = | No. of revolutions | |
s | 1 [unit] | |||
|
|
Level
3
The following equation determines the number of motor shaft revolutions to stop:
Revolutions Motor = P2488⋅ P2484⋅ P2482P2481
Index:
P2484[0] : 1st. Drive data set (DDS)
P2484[1] : 2nd. Drive data set (DDS)
P2484[2] : 3rd. Drive data set (DDS)
P2488[3] Distance / No. of revolutions |
| Min: | 0.01 | Level | |||
| CStat: | CUT | Datatype: Float | Unit: - | Def: | 1.00 | 3 |
|
| ||||||
| CONTROL | Active: first confirm | QuickComm.: No | Max: | 9999.99 |
|
Sets the required distance or number of revolutions (see P2484).
Motor Gear
f | s = P2488= | 1 | ⋅ f OFF1 . t P2488 |
| OFF1 | 2 |
|
fOFF1 |
|
| |
|
|
| |
| tP2488 | t |
|
|
|
|
Index:
P2488[0] : 1st. Drive data set (DDS)
P2488[1] : 2nd. Drive data set (DDS)
P2488[2] : 3rd. Drive data set (DDS)
r2489 | Act. number of shaft revolutions |
| Min: | - | Level |
| Datatype: Float | Unit: - | Def: | - | 3 |
|
| ||||
|
|
| Max: | - |
|
Displayes the actual number of shaft revolutions since trigger of positioning.
Note:
Positioning ramp down is an open loop control method. So, there might be a difference between the position setpoint and the calculated actual position shown in r2489. That means, it could happen that the setpoint position is already reached, although r2489 displays a different actual position .
240 | MICROMASTER 440 Parameter List |