Parameter Description | Issue 01/06 |
P2040 | CB telegram off time |
|
| Min: | 0 | |
| CStat: | CT | Datatype: U16 | Unit: ms | Def: | 20 |
| COMM | Active: Immediately | QuickComm.: No | Max: | 65535 |
Defines time after which a fault will be generated (F0070) if no telegram is received via the link.
Level
3
The telegramm off time defines the time, within which a valid telegram must be received. If no valid telegram is received within that time, the inverter trips with F0070.
Dependency:
Setting 0 = watchdog disabled
P2041[5] CB parameter |
|
| Min: | 0 | |
CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
COMM | Active: first confirm | QuickComm.: No | Max: | 65535 |
Configures a communication board (CB).
Index:
P2041[0] : CB parameter 0
P2041[1] : CB parameter 1
P2041[2] : CB parameter 2
P2041[3] : CB parameter 3
P2041[4] : CB parameter 4
Details:
See relevant communication board manual for protocol definition and appropriate settings.
Level
3
r2050[8] CO: PZD from CB |
| Min: | - |
Datatype: U16 | Unit: - | Def: | - |
| Max: | - |
Displays PZD received from communication board (CB).
Level
3
|
|
|
| r2050 |
|
|
|
|
| [0] | r2090 |
|
|
|
| [1] |
|
|
|
|
| [2] |
|
|
|
|
| [3] |
|
|
|
|
| . |
|
|
|
|
| . | r2091 |
PZD4 | PZD3 | PZD2 | PZD1 | . | |
[7] |
| ||||
STW2 |
| HSW | STW1 |
|
PZD | PKW |
Process data | Parameter |
P2041[0] CB telegram
PKW Parameter ID value PZD Process data
STW Control word HSW Main setpoint
CB on COM link PZD mapping to parameter 2050r
Index:
r2050[0] : Received word 0
r2050[1] : Received word 1
r2050[2] : Received word 2
r2050[3] : Received word 3
r2050[4] : Received word 4
r2050[5] : Received word 5
r2050[6] : Received word 6
r2050[7] : Received word 7
Note:
The control words can be viewed as bit parameters r2090 and r2091.
Restrictions:
-If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be transferred in the 1st
-If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the 2nd
-When P2012 is greater than or equal to 4 the additional control word (2nd control word) must transferred in the 4th
204 | MICROMASTER 440 Parameter List |