Issue 01/06 | Parameter Description |
Index:
P1233[0] : 1st. Drive data set (DDS)
P1233[1] : 2nd. Drive data set (DDS)
P1233[2] : 3rd. Drive data set (DDS)
Value:
P1233 = 0.00 :
Not active following OFF1 / OFF3.
P1233 = 0.01 - 250.00 :
Active for the specified duration.
Caution:
With the DC braking, the kinetic energy of the motor is converted into heat in the motor. The drive could overheat if the remains in this status for an exessive period of time !
DC braking is not possible when using a synchronous motor (i.e. P0300 = 2).
Notice:
The DC braking function causes the motor to stop rapidly by applying a DC braking current (the current applied also holds the shaft stationary). When the DC braking signal is applied, the inverter output pulses are blocked and the DC current not applied until the motor has been sufficiently demagnetized. Demagnetization time is calculated automatically from motor data.
The inverter will not restart if an
P1234[3] DC braking start frequency |
| Min: | 0.00 | ||
CStat: | CUT | Datatype: Float | Unit: Hz | Def: | 650.00 |
| FUNC | Active: Immediately | QuickComm.: No | Max: | 650.00 |
Sets start frequency for DC braking.
Level
2
When an OFF1 or OFF3 command is received by the drive, the output frequency starts to ramp to 0 Hz. When the output frequency reaches the value set in start frequency of DC braking P1234, the drive injects a DC braking current P1232 for the time duration set in P1233.
Index:
P1234[0] : 1st. Drive data set (DDS)
P1234[1] : 2nd. Drive data set (DDS)
P1234[2] : 3rd. Drive data set (DDS)
Details:
See P1232 (DC braking current) and P1233 (duration of DC braking)
MICROMASTER 440 | Parameter List |
145 |