Faults and AlarmsIssue 01/06
F0054 Incorrect I/O module | STOP II |
Quit
Refer to F0001
Cause
-incorrect I/O module inserted.
-no ID of the I/O module found, no data.
Diagnosis & Remedy
Please check the following:
-check I/O data, if required repeat the operation
-the installation of the I/O module in the inverter if required, replace the I/O module
F0060 Asic time slice overflow | STOP II |
Quit
Refer to F0001
Cause
-internal communications failure/error
Diagnosis & Remedy
-if the error still occurs, replace the inverter.
-contact customer service!
F0070 CB setpoint fault | STOP II |
Quit
Refer to F0001
Cause
-no setpoints received via the communications bus during the telegram failure time.
Diagnosis & Remedy
-check the communications module (CB) and communications partner.
F0071 USS(BOP link) setpoint fault | STOP II |
Quit
Refer to F0001
Cause
-no setpoint was received via the USS during the telegram off time
Diagnosis & Remedy
-check USS master
F0072 USS(COMM link) setpoint fault | STOP II |
Quit
Refer to F0001
Cause
- no setpoints received via the USS during the telegram off time
Diagnosis & Remedy
- check USS master
F0080 ADC input signal lost | STOP II |
Quit |
|
Refer to F0001 |
|
Cause |
|
- wire breakage |
|
- signal outside the limit values |
|
F0085 External fault | STOP II |
Quit |
|
Refer to F0001 |
|
Cause |
|
- external fault as a result of command input via terminals. |
|
Diagnosis & Remedy
-inhibit terminal input to initiate fault.