Parameter Description | Issue 01/06 |
r2026[2] | USS character frame error |
| Min: | - | |
|
| Datatype: U16 | Unit: - | Def: | - |
|
|
| Max: | - | |
Index: | Displays number of USS character frame errors. |
|
|
| |
r2026[0] | : Serial interface COM link |
|
|
| |
|
|
|
| ||
| r2026[1] | : Serial interface BOP link |
|
|
|
Level
3
r2027[2] USS overrun error |
| Min: | - |
Datatype: U16 | Unit: - | Def: | - |
| Max: | - |
Level
3
Displays number of USS telegrams with overrun error.
Index:
r2027[0] : Serial interface COM link
r2027[1] : Serial interface BOP link
r2028[2] USS parity error |
| Min: | - |
Datatype: U16 | Unit: - | Def: | - |
| Max: | - |
Level
3
Displays number of USS telegrams with parity error.
Index:
r2028[0] : Serial interface COM link
r2028[1] : Serial interface BOP link
r2029[2] | USS start not identified |
| Min: | - | Level | |
|
| Datatype: U16 | Unit: - | Def: | - | 3 |
|
|
| ||||
|
|
| Max: | - |
| |
Index: | Displays number of USS telegrams with unidentified start. |
|
|
| ||
r2029[0] | : Serial interface COM link |
|
|
|
| |
|
|
|
|
| ||
| r2029[1] | : Serial interface BOP link |
|
|
|
|
r2030[2] USS BCC error |
| Min: | - |
Datatype: U16 | Unit: - | Def: | - |
| Max: | - |
Level
3
Displays number of USS telegrams with BCC error.
Index:
r2030[0] : Serial interface COM link
r2030[1] : Serial interface BOP link
r2031[2] USS length error |
| Min: | - |
Datatype: U16 | Unit: - | Def: | - |
| Max: | - |
Level
3
Displays number of USS telegrams with incorrect length.
Index:
r2031[0] : Serial interface COM link
r2031[1] : Serial interface BOP link
r2032 | BO: CtrlWrd1 from BOP link (USS) |
| Min: | - | Level |
| Datatype: U16 | Unit: - | Def: | - | 3 |
|
| ||||
|
| Max: | - |
|
Displays control word 1 from BOP link (word 1 within USS).
Bitfields: |
|
|
|
|
|
Bit00 | ON/OFF1 | 0 | NO | 1 | YES |
Bit01 | OFF2: Electrical stop | 0 | YES | 1 | NO |
Bit02 | OFF3: Fast stop | 0 | YES | 1 | NO |
Bit03 | Pulses enabled | 0 | NO | 1 | YES |
Bit04 | RFG enable | 0 | NO | 1 | YES |
Bit05 | RFG start | 0 | NO | 1 | YES |
Bit06 | Setpoint enable | 0 | NO | 1 | YES |
Bit07 | Fault acknowledge | 0 | NO | 1 | YES |
Bit08 | JOG right | 0 | NO | 1 | YES |
Bit09 | JOG left | 0 | NO | 1 | YES |
Bit10 | Control from PLC | 0 | NO | 1 | YES |
Bit11 | Reverse (setpoint inversion) | 0 | NO | 1 | YES |
Bit13 | Motor potentiometer MOP up | 0 | NO | 1 | YES |
Bit14 | Motor potentiometer MOP down | 0 | NO | 1 | YES |
Bit15 | CDS Bit 0 (Local/Remote) | 0 | NO | 1 | YES |
202 | MICROMASTER 440 Parameter List |