Parameter Description |
|
|
|
| Issue 01/06 | |||
|
|
|
|
|
| |||
P0706[3] Function of digital input 6 |
| Min: | 0 |
| Level | |||
| CStat: | CT | Datatype: U16 | Unit: - | Def: | 15 |
| 2 |
|
|
| ||||||
| COMMANDS | Active: first confirm | QuickComm.: No | Max: | 99 |
|
|
Selects function of digital input 6.
Possible Settings:
0 | Digital input disabled | |
1 | ON/OFF1 | |
2 | ON reverse /OFF1 | |
3 | OFF2 | - coast to standstill |
4 | OFF3 | - quick |
9 | Fault acknowledge | |
10 | JOG right | |
11 | JOG left |
|
12 | Reverse | |
13 | MOP up | (increase frequency) |
14 | MOP down (decrease frequency) | |
15 | Fixed setpoint (Direct selection) | |
16 | Fixed setpoint (Direct selection + ON) | |
25 | DC brake enable | |
29 | External trip | |
33 | Disable additional freq setpoint | |
99 | Enable BICO parameterization | |
Index: |
|
|
P0706[0] : 1st. Command data set (CDS) | ||
P0706[1] : 2nd. Command data set (CDS) | ||
P0706[2] : 3rd. Command data set (CDS) | ||
Details: |
|
|
See P0701 (function of digital input 1). |
P0707[3] Function of digital input 7 |
| Min: | 0 | Level | |||
| CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 | 2 |
|
| ||||||
| COMMANDS | Active: first confirm | QuickComm.: No | Max: | 99 |
|
Selects function of digital input 7 (via analog input).
Possible Settings:
0Digital input disabled
1ON/OFF1
2ON reverse /OFF1
3 | OFF2 - coast to standstill |
4OFF3 - quick
9Fault acknowledge
10JOG right
11JOG left
12Reverse
13MOP up (increase frequency)
14MOP down (decrease frequency)
25DC brake enable
29External trip
33Disable additional freq setpoint
99Enable BICO parameterization
Index:
P0707[0] : 1st. Command data set (CDS)
P0707[1] : 2nd. Command data set (CDS)
P0707[2] : 3rd. Command data set (CDS)
Note:
Signals above 4 V are active, signals below 1,6 V are inactive.
Details:
See P0701 (function of digital input 1).