Parameter Description | Issue 01/06 |
P1133[3] |
| Min: | 0.00 | ||
CStat: | CUT | Datatype: Float | Unit: s | Def: | 0.00 |
SETPOINT | Active: first confirm | QuickComm.: No | Max: | 40.00 |
Defines rounding time at end of
Index:
P1133[0] : 1st. Drive data set (DDS)
P1133[1] : 2nd. Drive data set (DDS)
P1133[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1130.
Level
2
P1134[3] Rounding type |
|
| Min: | 0 | |
CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 |
SETPOINT | Active: Immediately | QuickComm.: No | Max: | 1 |
Level
2
Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g. new setpoint, OFF1, OFF3, REV).
This smoothing is applied, if the motor is
-P1134 = 0,
-P1132 > 0, P1133 > 0 and
-the setpoint is not yet reached.
P1132 > 0, P1133 > 0
f
fSet Setpoint reached
Setpoint not reached
P1134 = 0
t
P1132 | P1133 | P1132 | P1133 |
f
Setpoint reached
fSet
Setpoint not reached
P1134 = 1
|
| t |
P1132 | P1133 | P1133 |
ON |
|
|
OFF1 |
| t |
Possible Settings:
0Continuous smoothing
1Discontinuous smoothing
Index:
P1134[0] : 1st. Drive data set (DDS)
P1134[1] : 2nd. Drive data set (DDS)
P1134[2] : 3rd. Drive data set (DDS)
Dependency:
No effect until P1132
134 | MICROMASTER 440 Parameter List |