Parameter Description | Issue 01/06 |
r1527 | CO: Lower torque limitation |
| Min: | - |
| Datatype: Float | Unit: Nm | Def: | - |
|
| Max: | - |
Displays actual lower torque limitation.
Details:
See parameter r1526.
Level
3
P1530[3] Motoring power limitation |
| Min: | 0.00 | ||
CStat: | CUT | Datatype: Float | Unit: - | Def: | 0.12 |
CONTROL | Active: Immediately | QuickComm.: No | Max: | 8000.00 |
Level
2
Defines fixed value for the max. permissible motoring active power (motoring power limitation).
P1530def = 2.5 ⋅ P0307
P1530max = 3 ⋅ P0307
Parameter P1530 limits the torque in addition to the act. frequency as displayed in the following characteristic.
Power limitation (motoring, regenerative)
M = | P | M |
| ||
2 ⋅ π ⋅ f |
|
P1530
P1531
f
P1530
P1531
Index: |
|
P1530[0] | : 1st. Drive data set (DDS) |
P1530[1] | : 2nd. Drive data set (DDS) |
P1530[2] | : 3rd. Drive data set (DDS) |
P1531[3] Regenerative power limitation |
| Min: | Level | ||||
| CStat: | CUT | Datatype: Float | Unit: - | Def: | 2 | |
|
| ||||||
| CONTROL | Active: Immediately | QuickComm.: No | Max: | 0.00 |
|
Enters fixed value for the max. permissible regenerative active power (regenerative power limitation).
P1531def = - 2.5⋅ P0307
P1531max = - 3 ⋅ P0307
Index:
P1531[0] : 1st. Drive data set (DDS)
P1531[1] : 2nd. Drive data set (DDS)
P1531[2] : 3rd. Drive data set (DDS)
Details:
See parameter P1530.
r1536 | CO: Max. trq. motoring current |
| Min: | - | Level |
| Datatype: Float | Unit: A | Def: | - | 4 |
|
| ||||
|
| Max: | - |
|
Displays maximum torque motoring current component.
r1537 | CO: Max trq regenerative current |
| Min: | - |
| Datatype: Float | Unit: A | Def: | - |
|
| Max: | - |
Level
4
Displays maximum torque of the regenerative current component.
178 | MICROMASTER 440 Parameter List |