Command Set | 5017/5018 |
| Analog Input |
$aaSiB |
|
Name Configuration Status
Description Returns the configuration status parameters for a specified analog input module of a specified system.
Syntax | $aaSiB(cr) | |
| $ is a delimiter character. | |
| aa (range | |
| address of the | |
| interrogate. | |
| Si identifies the I/O slot you want to read. | |
| B is configuration status command. | |
| (cr) is the terminating character, carriage return (0Dh) | |
Response | !aarrff(cr) if the command is valid. | |
| ?aa(cr) if an invalid operation was entered. | |
| There is no response if the module detects a syntax error | |
| or communication error or if the specified address does | |
| not exist. | |
| ! delimiter character indicating a valid command was | |
| received. | |
| ? delimiter character indicating the command was | |
| invalid. | |
| aa (range | |
| address of an | |
| rr represents the | |
| input range. | |
| ff is a hexadecimal number that equals the | |
| ter representing data format. Bit 0 and 1 represent data | |
| format. Bit 7 represents integration time. (See Configura- | |