Command Set | 5017/5018 | |
|
| Analog Input |
$aaSiER |
|
|
Name | Initialize EEPROM data |
|
Description Initializes all EEPROM data in a specified analog input module to their default values. This command is sent following a failed attempt to calibrate a module (the module shows no effect from an attempted calibration). Following initialization, the problem module should readily accept calibration.
Syntax | $aaSiER(cr) |
| $ is a delimiter character. |
| aa (range |
| address of the |
| Si identifies the I/O slot for which you wish to initialize |
| all EEPROM data. |
| ER is Initialize all EEPROM data command. |
| (cr) is the terminating character, carriage return (0Dh) |
Response | !aa(cr) if the command is valid. |
| ?aa(cr) if an invalid operation was entered. |
| There is no response if the module detects a syntax error |
| or communication error or if the specified address does |
| not exist. |
| ! delimiter character indicating a valid command was |
| received. |
| ? delimiter character indicating the command was |
| invalid. |
aa(range
address of an | |
(cr) is the terminating character, carriage return (0Dh) | |
|
|