Command Set

5017/5018

 

 

Analog Input

$aaSiER

 

 

Name

Initialize EEPROM data

 

Description Initializes all EEPROM data in a specified analog input module to their default values. This command is sent following a failed attempt to calibrate a module (the module shows no effect from an attempted calibration). Following initialization, the problem module should readily accept calibration.

Syntax

$aaSiER(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system.

 

Si identifies the I/O slot for which you wish to initialize

 

all EEPROM data.

 

ER is Initialize all EEPROM data command.

 

(cr) is the terminating character, carriage return (0Dh)

Response

!aa(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

aa(range 00-FF) represents the 2-character hexadecimal

address of an

ADAM-5000 system.

(cr) is the terminating character, carriage return (0Dh)

 

 

6-50