Command Set | Analog Input Alarm |
5013/5017/5017H/5017UH/5018/5018P
$aaSiCjRhc
Name Read Alarm Connection
Description Returns the High/Low alarm limit output connection of a
| specified input channel in the addressed |
| system |
Syntax | $aaSiCjRhC(cr) |
| $ is a delimiter character. |
| aa (range |
| address of an |
| SiCj identifies the desired slot i (i : 0 to 3) and the |
| desired analog input channel j (j : 0 to 7). |
| RhC is the Read Alarm Connection command. |
| h indicates alarm type and can have the value H = High |
| alarm, L = Low alarm |
| (cr) represents terminating character, carriage return |
| (0Dh) |
Response | !aaSkCn(cr) if the command was valid |
| There is no response if the system detects a syntax error |
| or communication error or if the specified address does |
| not exist. |
| ! delimiter character indicating a valid command was |
| received. |
| aa represents the |
| corresponding |
| SkCn identifies the desired slot k (k : 0 to 3) and the |
| desired digital output point n (n : 0 to F) to which the |
| input alarm is connected. If the values of k and n are ‘*’, |
| the analog input has no connection with a digital output |
| point. |