ADAM-4000/5000 System Grounding Installation
E.6 Some Suggestions on Wiring Layout
Since communication is carried through
Generally, factories will layout the power lines, control lines, signal lines and communication lines within separate conduits. Since communication lines and signal lines are most susceptible to interference, you should consider avoid laying them parallel with any power line in close distance. Nevertheless, if they should remain parallel with the power line, just keep a proper distance between them. Basically, an AC current up to 2A should require a distance of 50 cm. The bigger the current or voltage, the longer the distance is required.
For communication lines and AI/O signal lines, it is suggested that they should be carried within
While planning your wire layouts, you should consider layouts that can save wire length.
|